The tiles on a tile-hung wall don’t count in its U-value: BR 443 (§4.7.1) treats the space behind tile hanging as a well-ventilated cavity, so the tiles, the battens and that space are left out, and the outside surface resistance rises from 0.04 to 0.13. A 1930s tile-hung cavity wall — brick both leaves and a 50mm empty cavity — comes out at about 1.28 W/m²K, against 1.44 for the same wall below the tiles. Filled with 50mm of blown mineral wool it is about 0.54, inside the 0.55 Approved Document L asks of cavity fill. Re-hanging the tiles over 100mm of PIR on a 9-inch solid wall gives about 0.21, inside the 0.30 for external insulation.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- Clay plain tiles on 38 × 25mm battens (a well-ventilated space: disregarded)
- 102.5mm brick outer leaf (λ 0.77, BR 443’s outer-leaf value)
- 50mm unventilated cavity
- 102.5mm brick inner leaf
- 13mm plaster
Clay tiles on battens are entered as cladding outside a well-ventilated air space, so U-Monkey disregards them and uses an outside surface resistance of 0.13 (BS EN ISO 6946 §6.9.4; BR 443 §4.7.1, §4.7.3). The outer leaf behind the tiles is taken at BR 443’s outer-leaf value, λ 0.77 (§3): its protected value behind cladding, 0.56, is written for solid walls (§7), and one row shows it. A solid wall behind tiles is taken as protected. Screws through insulation behind re-hung tiles are U-Monkey’s “EWI screw fixings” preset (6 per m², stainless). The link opens as an existing cavity wall being filled, judged against Approved Document L’s 0.55 (2021 edition, Table 4.3).
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| 1930s tile-hung cavity wall: brick both leaves, 50mm empty cavity | ≈ 1.28 | As pre-filled |
| The same, with the outer leaf taken as protected brick (λ 0.56) | ≈ 1.20 | BR 443 §7 gives the protected value behind cladding to a solid wall, not to an outer leaf |
| The same wall untiled (ground floor) | ≈ 1.44 | Outside surface 0.04 |
| 50mm blown mineral wool cavity fill (λ 0.040) | ≈ 0.54 | Meets 0.55 for cavity fill (0.540) |
| 9-inch solid brick, tile-hung | ≈ 1.57 | A solid wall behind cladding: protected brick (BR 443 §7), its mortar joints counted (§4.2) |
| 9-inch solid brick, tile-hung, brick at 0.77 | ≈ 1.77 | |
| 9-inch wall re-hung over 100mm PIR, 6 stainless screws per m² through it | ≈ 0.21 | Meets 0.30; of the usual board thicknesses, 70mm is the thinnest that does (0.284) |
| 9-inch wall re-hung over 120mm wood fibre (λ 0.041), screws as above | ≈ 0.30 | Meets 0.30, just: 0.296 |
| Counted the wrong way: tiles and a still air space, outside surface 0.04 | ≈ 1.13 | Understates the U-value by 0.15 |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
The tiles are cladding, not insulation. BR 443 takes the air behind tile hanging as well ventilated (§4.7.1), at the outside temperature, so everything outside it drops out, and because the cladding shelters the wall from the wind the outside surface resistance becomes 0.13 rather than 0.04 (§4.7.3); counting the tiles and a still air space instead understates the U-value by about a tenth. Behind the tiles the brick stays drier, but BR 443 gives brick its protected λ, 0.56, behind “an external insulation or cladding system” only in a solid wall (§7); for the outer leaf of a cavity wall its value is 0.77 “unless otherwise specified” (§3), and that is what U-Monkey uses here. Taken as protected, the wall would be 1.20. A solid 9-inch wall behind tiles does take the protected value. From there the usual routes apply. A 50mm cavity can be filled (0.54 with blown mineral wool at λ 0.040), and the tiles keep driving rain off the outer leaf, which is what tile hanging has long been used for. Stripping and re-hanging the tiles is the chance to put insulation behind them: on a 9-inch wall, 100mm of PIR gives about 0.21 with the screws through it, and 120mm of wood fibre about 0.30. Or insulate inside and leave the tiles alone.
Condensation and mould with a tile-hung wall
The empty 1930s wall fails U-Monkey’s surface-mould check — fRsi 0.69 against the 0.75 a home needs — as most uninsulated walls do; filling the cavity lifts it to 0.87. The filled wall gets a conditional pass in the BS EN ISO 13788 check: seasonal condensation against the back of the outer leaf, peaking at about 490 g/m² in March, that dries out over the summer — the usual Glaser result for a filled cavity. The check itself says it can’t settle this one alone: the result turns on the brick’s vapour resistance, which BS 5250 gives only as a wide range, and a Glaser calculation doesn’t model rain or the liquid moisture that brick carries, so its figures are indicative. Insulation behind re-hung tiles, PIR or wood fibre, passes with no condensation in any month: it keeps the whole wall warm. Keep the batten space ventilated and drained, with an underlay behind the battens.
Opens pre-filled. The condensation verdict sits just under the U-value — tap it for the full month-by-month check, the surface-mould (fRsi) check included. If it isn’t a pass, How to fix it tests the usual remedies on your build-up — a vapour control layer on the warm side, a more vapour-open layer on the cold side, more insulation to warm the inside surface — and applies the one you pick in a tap, with Undo.
Need it in writing for Building Control? The full condensation risk analysis report is £25 +VAT (£30 inc VAT), or included on Monkey Pro Unlimited — see an example report (PDF), or read what building control expects the analysis to show.
It is a screening to BS EN ISO 13788 (the Glaser method), honestly labelled as one: it does not model air leakage, rain or moisture stored in materials, so for high-risk or heritage constructions a full hygrothermal simulation (BS EN 15026) is the right next step. Figures above use the app’s defaults — Manchester (Ringway) climate, humidity class 3 (dwellings with high or unknown occupancy), a 1-in-10 design year and, on a roof, the surface taken 2 K below the air for night-sky cooling — so pick your nearest weather station for your own build-up: the result can change from one station to another.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a tile-hung wall?
The tiles on a tile-hung wall don’t count in its U-value: BR 443 (§4.7.1) treats the space behind tile hanging as a well-ventilated cavity, so the tiles, the battens and that space are left out, and the outside surface resistance rises from 0.04 to 0.13. A 1930s tile-hung cavity wall — brick both leaves and a 50mm empty cavity — comes out at about 1.28 W/m²K, against 1.44 for the same wall below the tiles. Filled with 50mm of blown mineral wool it is about 0.54, inside the 0.55 Approved Document L asks of cavity fill. Re-hanging the tiles over 100mm of PIR on a 9-inch solid wall gives about 0.21, inside the 0.30 for external insulation.
Do I have to insulate when I re-hang tile hanging?
Possibly. The Building Regulations count the replacement of a layer of a wall as renovating it (regulation 2(1)), and renovating more than half of a wall’s area brings in the upgrade Approved Document L asks for — 0.30 for external insulation — so far as that is technically, functionally and economically feasible, with a simple payback of 15 years or less (regulation 23; Approved Document L, paragraphs 4.12 and 4.13). Whether stripping and re-hanging the tiles counts that way is for building control, so ask before you start; if it does, 70–100mm of PIR or about 120mm of wood fibre behind the new tiles is the usual answer on a 9-inch wall.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.