A 600mm cob wall, lime-rendered outside and lime-plastered inside, has a calculated U-value of about 0.82 W/m²K, taking λ 0.6 for the cob — the middle of a published range that runs from 0.45, the mean Goodhew & Griffiths give for Devon cob at 1450 kg/m³, to 0.73, a Devon Earth Building Association figure the SPAB used in its U-value research, which puts the same wall anywhere between 0.64 and 0.96. Measurement agrees: most of the SPAB’s in-situ readings on cob walls came out between 0.76 and 1.05, and RdSAP assumes 0.80 for a cob wall as built. Insulating one is about moisture as much as heat: 60mm of wood-fibre board inside gives about 0.36, and 250mm of hempcrete outside about 0.21.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- 20mm lime render
- 600mm cob (earth and straw, λ 0.6)
- 15mm lime plaster
Cob at λ 0.6 from U-Monkey’s library, inside the published range: Goodhew & Griffiths (2005) give 0.45 for Devon cob at 1450 kg/m³, and a Devon Earth Building Association figure of 0.73 that the SPAB used in its U-value research. The SPAB’s measured walls (Rye & Scott, Research Report 1, 2012) were about 400–620mm of cob. RdSAP figures are from RdSAP 10, Table 6 (England, age bands A–F). The pre-filled link opens as an existing element.
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| 450mm cob | ≈ 1.03 | |
| 500mm cob | ≈ 0.95 | |
| 600mm cob | ≈ 0.82 | As pre-filled |
| 700mm cob | ≈ 0.72 | |
| 600mm at λ 0.45 (Devon cob mean, Goodhew & Griffiths 2005) | ≈ 0.64 | |
| 600mm at λ 0.73 (Devon Earth Building Association, as the SPAB used) | ≈ 0.96 | |
| 600mm + 60mm wood-fibre board inside, lime plaster | ≈ 0.36 | U-Monkey’s condensation check: screening only |
| 600mm + 100mm wood-fibre board inside | ≈ 0.26 | Meets the 0.30 for an upgraded wall |
| 600mm + 250mm hempcrete outside (λ 0.07) | ≈ 0.21 | A Plymouth study of this wall gives about 0.3 with its hempcrete |
| 600mm + 40mm cork-lime render outside (λ 0.09) | ≈ 0.61 | λ from Secil’s data sheet FT 12004.04 (April 2024); an older distributor sheet gave 0.10 |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
The cob’s conductivity is the big unknown: it depends on the earth, the straw and above all the density and the moisture in the wall, and calculation is often pessimistic for traditional walls — the SPAB’s research found it overestimated the U-value in 77% of the walls it measured (Research Report 1, 2012). For an existing wall, a measured U-value (BS ISO 9869) is worth having before deciding how much insulation it needs. Whatever goes on has to let the wall keep drying: Historic England notes that materials highly resistant to the passage of water vapour or liquid water are not usually appropriate for a traditionally constructed building, and risk trapping moisture in the fabric. So the usual choices are vapour-open ones — wood fibre or cork inside with lime plaster, hemp-lime or cork-lime outside — on a wall kept dry at its base, which in historic earth buildings means a masonry plinth. Inside insulation needs the most care: U-Monkey’s check predicts seasonal condensation where the wood-fibre board meets the old plaster — about 1.1 kg/m² by March with 60mm, 1.7 kg/m² by April with 100mm — that dries out in summer, and calls it a screening result, because wood fibre and earth move water by capillary action, which a Glaser calculation can’t model; a BS EN 15026 assessment by a specialist is the next step. RdSAP assumes a 540mm cob wall and 0.80 W/m²K for one built before 1983, and gives 0.40 with 50mm of insulation added and 0.26 with 100mm.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a cob wall?
A 600mm cob wall, lime-rendered outside and lime-plastered inside, has a calculated U-value of about 0.82 W/m²K, taking λ 0.6 for the cob — the middle of a published range that runs from 0.45, the mean Goodhew & Griffiths give for Devon cob at 1450 kg/m³, to 0.73, a Devon Earth Building Association figure the SPAB used in its U-value research, which puts the same wall anywhere between 0.64 and 0.96. Measurement agrees: most of the SPAB’s in-situ readings on cob walls came out between 0.76 and 1.05, and RdSAP assumes 0.80 for a cob wall as built. Insulating one is about moisture as much as heat: 60mm of wood-fibre board inside gives about 0.36, and 250mm of hempcrete outside about 0.21.
Do I have to insulate a cob wall when I renovate it?
Not necessarily. In England, renovating more than half of a wall — re-rendering it, say — normally brings in Approved Document L’s improved value for an existing wall, 0.30 W/m²K (Table 4.3), where that is technically, functionally and economically feasible (paragraph 4.13). But paragraph 0.10 says the energy efficiency of a historic or traditional dwelling should be improved only where that will not cause long-term deterioration of its fabric or fittings, and names cob among the vapour-permeable constructions this applies to; for a listed building or one in a conservation area, the standards apply only so far as they would not unacceptably alter its character or appearance (paragraphs 0.8–0.9). Agree what is reasonable with building control, and with the conservation officer where the building is listed.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.