A 215mm (9-inch) solid brick wall with 13mm of dense plaster has a calculated U-value of about 2.1 W/m²K, using BR 443’s conductivity for brickwork exposed to the weather (λ 0.77). That is the figure a U-value calculation, and so a Part L appraisal of the wall, starts from. Real walls usually do better: BRE measured 85 solid brick walls in English homes in 2014 and found an average of 1.57, and RdSAP 10 now assumes 1.7 for a wall 200–280mm thick. Whichever you use, it is far above the 0.70 at which Approved Document L counts a wall as one to upgrade, and about twelve times the 0.18 of a new-build wall.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- 215mm solid brickwork (9-inch, the bricks laid across the wall)
- 13mm dense gypsum plaster
The pre-filled link opens as an existing element, judged against Approved Document L’s 0.70 threshold (2021 edition, Table 4.3). Brick at BR 443’s λ 0.77 throughout; there is no cavity, so no air-gap correction or wall ties.
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| 215mm brick, unplastered | ≈ 2.23 | A garage or outbuilding wall |
| 215mm brick + 20mm lime plaster | ≈ 2.09 | Lime instead of gypsum makes almost no difference |
| 215mm brick + 13mm dense plaster | ≈ 2.10 | The calculated figure, as pre-filled |
| RdSAP 10 default, solid brick 200–280mm | 1.7 | An assumed value for EPCs, down from 2.1 after BRE’s field measurements (CONSP:16, 2016) |
| Measured: 85 solid brick walls (BRE, 2014) | 1.57 (mean) | In-situ heat-flux measurements; the same walls calculated at 1.90 on average |
| One-and-a-half brick (327.5mm) + plaster | ≈ 1.61 | See the 1½-brick wall page |
| Half brick (102.5mm) + plaster | ≈ 3.04 | Single-skin extensions and outbuildings |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
Nothing about a bare wall moves the number much except its thickness: 215 to 327.5mm takes it from 2.1 to 1.6. The calculation uses BR 443’s λ 0.77, the cautious value for brick that gets wet; drier brick, lime mortar and the air in the joints are why measured walls come out lower. Neither figure changes the answer, which is insulation — internal or external — and on a solid wall that is a moisture decision as much as a thermal one. U-Monkey opens this wall as an existing element, judged against the 0.70 threshold; switch the work type to “upgrade” and add a lining to see what reaches the 0.30 Approved Document L asks of an insulated wall.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a solid brick wall (9-inch, uninsulated)?
A 215mm (9-inch) solid brick wall with 13mm of dense plaster has a calculated U-value of about 2.1 W/m²K, using BR 443’s conductivity for brickwork exposed to the weather (λ 0.77). That is the figure a U-value calculation, and so a Part L appraisal of the wall, starts from. Real walls usually do better: BRE measured 85 solid brick walls in English homes in 2014 and found an average of 1.57, and RdSAP 10 now assumes 1.7 for a wall 200–280mm thick. Whichever you use, it is far above the 0.70 at which Approved Document L counts a wall as one to upgrade, and about twelve times the 0.18 of a new-build wall.
Why is a solid wall 2.1 in one place and 1.7 in another?
2.1 is the calculation: BS EN ISO 6946 with BR 443’s conductivity for brick. 1.7 is RdSAP 10’s default for a solid brick wall 200–280mm thick (Table 13 of the June 2026 specification, version 4.0), which BRE proposed in 2016 after measuring 85 solid brick walls in English homes and finding an average of 1.57 W/m²K, against 1.90 calculated for the same walls and the 2.1 RdSAP then assumed. An EPC uses the default; a U-value calculation for Building Control uses the conductivities, so it gives the higher figure. Both say the wall loses heat roughly ten times faster than a new one.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.