A mansard’s steep face, with 150mm of PIR (λ 0.022) between 47 × 150mm rafters at 400mm centres and 52.5mm of insulated plasterboard under them, has a U-value of about 0.15 W/m²K (0.146). That meets both values it might be held to under Approved Document L for a loft conversion — 0.15 for a new roof and 0.18 for a new wall in an existing home — and which one applies isn’t settled: energy-modelling conventions treat a pitch of 70° or more as a wall, while Approved Document L doesn’t say, so ask building control. Framed as a stud wall instead, at BR 443’s 15% timber-frame default, the same build-up is 0.152 and needs a 62.5mm board for the roof value (0.141). 100mm between the rafters and a 62.5mm board gives 0.16: enough for a wall, not for a roof. The slates count for nothing: the space behind them is well ventilated, so BR 443 (§4.7.1) leaves them out.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- Natural slate on battens and counter-battens (a well-ventilated space: disregarded)
- Breather membrane
- 150mm PIR (λ 0.022) between 47 × 150mm rafters at 400mm centres (12.8% timber)
- 52.5mm insulated plasterboard (40mm PIR + 12.5mm board), joints taped
Calculated as a wall at 70°: heat flow within 30° of horizontal counts as horizontal (BR 443 §4.1), with the slate and its batten space disregarded (§4.7.1, §4.7.3). The timbers are rafters, at width ÷ spacing + 0.01 (§4.5); two rows show a stud-framed mansard at BR 443’s 15%. The insulated plasterboard is entered as its PIR core and a 12.5mm board. The link opens as a new element in an existing home, judged against the wall value, 0.18 (Approved Document L 2021, Table 4.2); the roof value for the same work is 0.15.
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| 100mm PIR between 150mm rafters (50mm gap outside it) + 62.5mm insulated plasterboard | ≈ 0.16 | Meets 0.18 (wall), misses 0.15 (roof); the gap beside the PIR’s foil face counts as a low-emissivity cavity |
| 100mm between + 52.5mm board | ≈ 0.17 | Meets 0.18 only |
| 100mm between + 72.5mm board | ≈ 0.15 | Meets both |
| 120mm between + 52.5mm board | ≈ 0.16 | |
| 150mm between (full) + 37.5mm board | ≈ 0.16 | Misses 0.15 (0.165) |
| 150mm between + 52.5mm board | ≈ 0.15 | As pre-filled: meets both (0.146) |
| 150mm between + 62.5mm board | ≈ 0.14 | |
| 150mm between, plain plasterboard | ≈ 0.22 | One layer: the rafters bridge it, and air-gap level 1 |
| Rafters at 600mm (8.8%): 100mm between + 62.5mm board | ≈ 0.15 | Misses 0.15 (0.152) |
| Framed as a stud wall (BR 443’s timber-frame default, 15%): 150mm + 52.5mm board | ≈ 0.15 | Misses 0.15 (0.152); meets 0.18 |
| Framed as a stud wall, 15%: 150mm + 62.5mm board | ≈ 0.14 | Meets both (0.141) |
| 150mm + 52.5mm, taken as a pitched roof (heat flow upwards) | ≈ 0.15 | 0.148 against 0.146: BR 443 takes heat flow as horizontal above 60° |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
Two things set a mansard apart from a pitched roof. The heat flow: BR 443 takes heat flowing within 30° of horizontal as horizontal (§4.1) — any slope steeper than 60° — so the inside surface takes the wall value, 0.13, not the roof’s 0.10 — calculated as a pitched roof the pre-filled build-up reads 0.148 rather than 0.146. And the slates: the space behind slates or tiles on battens is well ventilated (BR 443 §4.7.1), so the slates, the battens and that space are disregarded and the outside surface resistance becomes 0.13 (§4.7.3). After that it is the insulation and the timber. BR 443 has no default for rafters, so their share is width ÷ spacing + 0.01 (§4.5): 12.8% at 400mm centres, 8.8% at 600mm. A mansard framed as a stud wall — sole and head plates, noggings, trimmers round the dormers — takes BR 443’s timber-frame default of 15% instead (§4.4.1), which puts the pre-filled build-up at 0.152. A continuous layer under the timbers breaks that bridge and, as a second layer, takes the air-gap correction to level 0. Planning sets the angle: Camden’s guidance describes the lower slope as “usually 60-70°”, and Kensington and Chelsea’s order for Redcliffe Road sets 72°.
Condensation risk in a mansard
U-Monkey’s free BS EN ISO 13788 check finds no interstitial condensation in any month for the pre-filled mansard, with each assumed vapour value tested across its range: the breather membrane outside is vapour-open, and the insulated plasterboard’s foil and taped joints hold vapour back on the warm side. The places to watch are the junctions — the box gutter behind the parapet, the floor and the dormer cheeks — where the insulation is easily thinner than on the plane.
Opens pre-filled. The condensation verdict sits just under the U-value — tap it for the full month-by-month check, the surface-mould (fRsi) check included. If it isn’t a pass, How to fix it tests the usual remedies on your build-up — a vapour control layer on the warm side, a more vapour-open layer on the cold side, more insulation to warm the inside surface — and applies the one you pick in a tap, with Undo.
Need it in writing for Building Control? The full condensation risk analysis report is £25 +VAT (£30 inc VAT), or included on Monkey Pro Unlimited — see an example report (PDF), or read what building control expects the analysis to show.
It is a screening to BS EN ISO 13788 (the Glaser method), honestly labelled as one: it does not model air leakage, rain or moisture stored in materials, so for high-risk or heritage constructions a full hygrothermal simulation (BS EN 15026) is the right next step. Figures above use the app’s defaults — Manchester (Ringway) climate, humidity class 3 (dwellings with high or unknown occupancy), a 1-in-10 design year and, on a roof, the surface taken 2 K below the air for night-sky cooling — so pick your nearest weather station for your own build-up: the result can change from one station to another.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a mansard roof?
A mansard’s steep face, with 150mm of PIR (λ 0.022) between 47 × 150mm rafters at 400mm centres and 52.5mm of insulated plasterboard under them, has a U-value of about 0.15 W/m²K (0.146). That meets both values it might be held to under Approved Document L for a loft conversion — 0.15 for a new roof and 0.18 for a new wall in an existing home — and which one applies isn’t settled: energy-modelling conventions treat a pitch of 70° or more as a wall, while Approved Document L doesn’t say, so ask building control. Framed as a stud wall instead, at BR 443’s 15% timber-frame default, the same build-up is 0.152 and needs a 62.5mm board for the roof value (0.141). 100mm between the rafters and a 62.5mm board gives 0.16: enough for a wall, not for a roof. The slates count for nothing: the space behind them is well ventilated, so BR 443 (§4.7.1) leaves them out.
Is a mansard a roof or a wall for Building Regulations?
For energy, Approved Document L doesn’t draw the line. The National Calculation Methodology’s modelling guide for Scotland counts any part of a roof pitched at 70° or more as a wall, as the 2008 guide for England and Wales did, and RdSAP treats a mansard storey with slopes of at least 70° as a storey of its own; practice varies, so meeting the roof value, 0.15, avoids the argument. For fire it is defined: regulation 2(6) of the Building Regulations 2010 counts a roof pitched at more than 70° beside a space people use as part of the external wall. On a relevant building — one with a storey at least 18m above ground containing dwellings, an institution or rooms for residential purposes — regulation 7(2) then requires materials of class A2-s1, d0 or A1 there, which rules out PIR and a timber frame alike (membranes and some other components are exempt); and on a residential building with a storey over 11m, Approved Document B asks for insulation of class A2-s1, d0 or better in the external wall, or a BS 8414 test to BR 135. A slope of exactly 70° is a wall for energy modelling but not an external wall for regulation 7.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full roof U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.