A party wall’s U-value is assigned by its construction, not calculated from its layers: 0.5 W/m²K for an unfilled cavity with no effective edge sealing, 0.2 for an unfilled cavity effectively sealed at all its exposed edges, and 0.0 for a solid wall or a cavity that is fully filled and effectively sealed (SAP 10.2 Table 3.10; Approved Document L Table 2.1). The heat is not conducted to the neighbour: it is carried by air moving up through the cavity and out at the top — the party wall bypass, measured at Stamford Brook as an effective 0.50–0.63. Part L 2021’s notional dwelling assumes 0.0; the limiting value is 0.20.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- 12.5mm plasterboard on dabs
- 100mm lightweight aggregate block
- 75mm cavity fully filled with party wall roll, sealed at every exposed edge
- 100mm lightweight aggregate block
- 12.5mm plasterboard on dabs
U-Monkey assigns a party wall’s U-value from the construction you pick, as SAP 10.2 (Table 3.10) and Approved Document L (2021 edition, paragraph 2.14 and Table 2.1) do: the layers are shown, and used for thermal mass, but do not change it. The pre-filled link opens with the cavity fully filled and sealed.
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| Solid wall (masonry, or a SIP) | 0.0 | SAP 10.2 Table 3.10 |
| Cavity fully filled and effectively sealed at all exposed edges | 0.0 | As pre-filled |
| Unfilled cavity, effectively sealed at all exposed edges | 0.2 | |
| Unfilled cavity, no effective edge sealing | 0.5 | Worse than the 0.20 limiting value |
| Measured, unfilled cavities (Stamford Brook, 2007) | 0.50–0.63 | The effective U-value of the bypass |
| Home Energy Model: unfilled, unsealed, dry-lined | 0.6 | Behind wet plaster: 0.2 (HEM-TP-05) |
Party wall U-values are assigned by the construction (SAP 10.2 Table 3.10; Approved Document L 2021, Table 2.1), not calculated from the layers, and the pre-filled calculator applies the one you pick. The measured and Home Energy Model rows are figures from the sources named, for comparison.
What changes the number
Sealing and fill are the whole story. Sealing the cavity at the top, the bottom and the vertical edges — in line with the insulation of the roof, floor and external walls — stops the stack effect, and filling it stops air moving within it; only both together earn 0.0, and Approved Document L asks that the edge sealing be likely to be robust under normal site conditions (Table 2.1, note 1). Part E still applies: the fill and the seals must not spoil the wall’s sound insulation, and several Robust Details masonry separating walls (E-WM-17, E-WM-20 and E-WM-24, for example) now include a full-fill option with a named party wall roll. Under the Home Energy Model, one of the two routes in the 2026 edition of Approved Document L, the lining matters as well: an unfilled, unsealed cavity behind plasterboard on dabs counts as 0.6, behind wet plaster 0.2.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
- Party Wall Junction E18 / E25 / P1–P8
- Eaves Junction E10 / E11 / E24
- Wall-to-Floor Junction E5 / E19 / E22
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a party wall (0.0, 0.2 or 0.5)?
A party wall’s U-value is assigned by its construction, not calculated from its layers: 0.5 W/m²K for an unfilled cavity with no effective edge sealing, 0.2 for an unfilled cavity effectively sealed at all its exposed edges, and 0.0 for a solid wall or a cavity that is fully filled and effectively sealed (SAP 10.2 Table 3.10; Approved Document L Table 2.1). The heat is not conducted to the neighbour: it is carried by air moving up through the cavity and out at the top — the party wall bypass, measured at Stamford Brook as an effective 0.50–0.63. Part L 2021’s notional dwelling assumes 0.0; the limiting value is 0.20.
Do I have to fill a party wall cavity?
To claim 0.0, yes: fully filled and effectively sealed at every exposed edge. Sealing alone gets 0.2, and an open, unfilled cavity 0.5, which is worse than Approved Document L’s 0.20 limiting value for a party wall (Table 4.1). The fill has to be compatible with the wall’s sound insulation under Part E, so use a Robust Details specification with a full-fill option, or a design that is sound-tested.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — a party wall takes the U-value SAP 10.2 (Table 3.10) and Approved Document L (Table 2.1) assign to its construction; everything else uses the combined method of BS EN ISO 6946:2017 with BR 443 conventions, BS EN ISO 13370 for ground floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.