A knee wall with 100mm of PIR between the studs and a continuous 50mm PIR layer inside them, finished in plasterboard, has a U-value of about 0.18 W/m²K taking the eaves space behind it as outside air — just inside the 0.18 Approved Document L sets for a new wall in an existing home (0.1796). 40mm inside gives 0.20 and misses on that basis. SAP 10.2 treats the eaves as an unheated space and adds a resistance of 0.5 m²K/W for it (Table 3.4), which takes the pre-filled wall to about 0.16 and the 40mm version to 0.179, inside 0.18; U-Monkey applies it when you pick the loft void under “On the other side”.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- (The ventilated eaves space behind: taken as outside air)
- Breather membrane on the eaves face
- 100mm PIR between 100mm studs (15% timber)
- 50mm PIR across the inside of the studs (continuous)
- 12.5mm plasterboard
The pre-filled link opens as a new element in an existing home, judged against Approved Document L’s 0.18 (2021 edition, Table 4.2). The eaves are taken as outside air (Rse 0.04); SAP’s eaves allowance (SAP 10.2 and 10.3, Table 3.4) is the separate row, 1/(1/U + 0.5) — in the app, “On the other side”: the loft void behind the insulated wall of a room in roof.
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| Uninsulated: plasterboard on studs | ≈ 2.27 | |
| 50mm quilt between the studs | ≈ 0.84 | Many older rooms in roofs |
| 100mm PIR between the studs only | ≈ 0.35 | The studs bridge it |
| 100mm between + 25mm PIR inside | ≈ 0.23 | |
| 100mm between + 40mm PIR inside | ≈ 0.20 | Misses (0.197); 0.179 with SAP’s Ru |
| 100mm between + 50mm PIR inside | ≈ 0.18 | As pre-filled: 0.1796 |
| 100mm mineral wool between + 50mm PIR inside | ≈ 0.22 | |
| Pre-filled wall with SAP’s eaves allowance (Ru 0.5) | ≈ 0.16 | 1/(1/0.1796 + 0.5) = 0.1648 |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for. Rows that give an Ru include the unheated space beyond the element as an extra resistance, U = 1/(1/Uo + Ru) (SAP 10.2 §3.3 formula (3); BR 443 §5), which the calculator applies under “On the other side”.
What changes the number
The studs bridge 15% of the insulation between them, so the continuous layer inside does more per millimetre than extra depth: 100mm between the studs plus 25mm across them (0.23) beats 150mm between deeper studs (0.24). Many loft conversions avoid the knee wall as a thermal line altogether by insulating the roof slope right down to the eaves, which brings the eaves space inside; the knee wall then needs nothing, but the slope has to meet the roof figure all the way down. Where the knee wall is the line, the floor of the eaves space behind it — the ceiling of the room below — has to be insulated too, and the junctions sealed, or cold air from the ventilated eaves washes through the insulation.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a knee wall in a loft conversion?
A knee wall with 100mm of PIR between the studs and a continuous 50mm PIR layer inside them, finished in plasterboard, has a U-value of about 0.18 W/m²K taking the eaves space behind it as outside air — just inside the 0.18 Approved Document L sets for a new wall in an existing home (0.1796). 40mm inside gives 0.20 and misses on that basis. SAP 10.2 treats the eaves as an unheated space and adds a resistance of 0.5 m²K/W for it (Table 3.4), which takes the pre-filled wall to about 0.16 and the 40mm version to 0.179, inside 0.18; U-Monkey applies it when you pick the loft void under “On the other side”.
Can I count the eaves space behind a knee wall?
In a SAP calculation, yes: SAP 10.2 §3.3.5 gives an unheated-space resistance of 0.5 m²K/W (Table 3.4) for the insulated wall of a room in roof built into a roof insulated at ceiling level, for new dwellings and for conversions that create a room in roof, and BR 443 §5 says the effect of an unheated space can be incorporated into the U-value of the element. The pre-filled link takes the eaves as outside air, the cautious figure; pick “loft void behind the insulated wall of a room in roof” under “On the other side” and U-Monkey adds the 0.5. With Ru 0.5 the wall needs about 0.198 on its own to come out at 0.18, so ask your building control body which basis it will accept before thinning the lining.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.