A 215mm dense blockwork wall between a flat and an unheated access corridor, lined on the flat’s side with 82.5mm insulated plasterboard (70mm of PIR), has a U-value of about 0.24 W/m²K with the corridor counted the way SAP 10.2 counts it, and about 0.28 taking the corridor as outside air. SAP adds the corridor as an extra resistance, Ru, outside the wall — 0.6 m²K/W for a corridor whose facing wall is exposed, with corridors above and below (Table 3.3) — using U = 1/(1/Uo + Ru). Next to an unheated stairwell the allowance is much bigger, Ru 2.1 to 2.5, which takes the same wall to 0.16–0.17. If the corridor is heated — with controlled fixed heaters, in SAP’s conventions (5.03) — the wall counts as a party wall instead, and SAP gives a solid one a U-value of 0.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- (The unheated access corridor beyond: Ru 0.6, SAP 10.2 Table 3.3)
- 215mm dense concrete blockwork
- 15mm plaster dabs
- 82.5mm insulated plasterboard: 70mm PIR bonded to 12.5mm plasterboard
Ru from SAP 10.2 (and 10.3) Table 3.3, applied as SAP’s formula (3), U = 1/(1/Uo + Ru), where Uo is the wall calculated as if it faced outside air. The pre-filled link opens with “On the other side” set to this corridor. The insulated plasterboard is modelled as 70mm of PIR bonded to 12.5mm plasterboard, on dabs bridging 20% of the gap (BR 443 §4.6.1).
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| Facing outside air | ≈ 0.28 | Uo: 0.276, which misses the 0.26 limit |
| Access corridor, facing wall exposed, corridors above and below (Ru 0.6) | ≈ 0.24 | As pre-filled: 0.237 |
| Access corridor, facing wall exposed, corridor above or below (Ru 0.5) | ≈ 0.24 | 0.243 |
| Access corridor, facing wall not exposed, corridors above and below (Ru 0.9) | ≈ 0.22 | |
| Access corridor, facing wall not exposed, corridor above or below (Ru 0.7) | ≈ 0.23 | |
| Unheated stairwell, facing wall exposed (Ru 2.1) | ≈ 0.17 | Inside the 0.18 notional value: 0.175 |
| Unheated stairwell, facing wall not exposed (Ru 2.5) | ≈ 0.16 | |
| 60mm PIR (72.5mm board), corridor Ru 0.6 | ≈ 0.26 | Misses 0.26 even with the corridor: 0.264 |
| 50mm PIR (62.5mm board), corridor Ru 0.6 | ≈ 0.30 | |
| Unlined: 215mm dense block plastered both sides, corridor Ru 0.6 | ≈ 0.99 | 2.43 facing outside air |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for. Rows that give an Ru include the unheated space beyond the element as an extra resistance, U = 1/(1/Uo + Ru) (SAP 10.2 §3.3 formula (3); BR 443 §5), which the calculator applies under “On the other side”.
What changes the number
Ru depends on which surfaces of the corridor lose heat. SAP 10.2 Table 3.3 asks whether the corridor’s facing wall — the one opposite the flat — is an external wall, and whether there are corridors both above and below or only above or below (SAP’s Figure 3.1 shows the layouts); a stairwell gets far more, Ru 2.1–2.5. SAP 10 recalculated these values at one air change an hour, where SAP 2012 had used three, because buildings had become more airtight (BRE consultation paper CONSP:09), so its figures are much higher than SAP 2012’s 0.28–0.43 for corridors and 0.82–0.90 for stairwells: an older assessment of the same wall shows a higher U-value. The lining does the work either way — the 215mm of block is worth about 0.19 m²K/W, the 70mm of PIR about 3.2. The SAP conventions also give a window onto an unheated corridor a reduced U-value (5.17) and multiply the Ψ-values of junctions at the corridor or stairwell by 0.71–0.85 (5.12). U-Monkey’s condensation check takes the corridor as outside air; it finds no condensation in any month, but rates internal insulation on solid masonry as a screening result only.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a wall to an unheated corridor or stairwell in flats?
A 215mm dense blockwork wall between a flat and an unheated access corridor, lined on the flat’s side with 82.5mm insulated plasterboard (70mm of PIR), has a U-value of about 0.24 W/m²K with the corridor counted the way SAP 10.2 counts it, and about 0.28 taking the corridor as outside air. SAP adds the corridor as an extra resistance, Ru, outside the wall — 0.6 m²K/W for a corridor whose facing wall is exposed, with corridors above and below (Table 3.3) — using U = 1/(1/Uo + Ru). Next to an unheated stairwell the allowance is much bigger, Ru 2.1 to 2.5, which takes the same wall to 0.16–0.17. If the corridor is heated — with controlled fixed heaters, in SAP’s conventions (5.03) — the wall counts as a party wall instead, and SAP gives a solid one a U-value of 0.
What U-value does a wall to an unheated corridor need?
It is a thermal element: it separates the flat from an unconditioned part of the building (Building Regulations 2010, regulation 2(3)). In England, in a new block that means the 0.26 W/m²K limiting value for a wall (Approved Document L 2021, Table 4.1), and the notional dwelling that sets the energy targets gives “external walls including semi-exposed walls” 0.18 (Table 1.1). Where the common areas are unheated, Approved Document L also asks for their own fabric elements to meet the Section 4 standards (paragraph 0.4). SAP counts the corridor’s Ru in the energy calculation, and BR 443 §5 says the effect of an unheated space can be incorporated into the U-value of the element; whether your building control body checks the limiting value with it is worth agreeing first. The pre-filled wall meets 0.26 only with the corridor counted (0.237, against 0.276), and 60mm of PIR misses it even then (0.264).
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.