A 300mm cast hempcrete wall round a timber frame, lime-rendered outside and lime-plastered inside, has a U-value of about 0.23 W/m²K at λ 0.07 — inside the 0.26 limiting value for a new wall but short of the 0.18 notional value. The often-quoted 0.20 for 300mm needs λ 0.06, the figure given for Tradical Hemcrete at 275 kg/m³; denser mixes declared at 0.076–0.085 give 0.25–0.27, and the 0.27 misses the limit. 400mm at λ 0.07 gives about 0.17.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- 20mm lime render
- 125mm cast hempcrete (λ 0.07)
- 100mm hempcrete round 100mm timber studs (15% timber)
- 75mm hempcrete covering the studs inside
- 15mm lime plaster
Hempcrete at λ 0.07 (U-Monkey’s library; typical cast hemp-lime at 275–330 kg/m³). Sources for the variants: Lime Technology’s figure for Tradical Hemcrete as published by the Limecrete Company (0.06 at 275 kg/m³) and BCB-Tradical’s 2016 brochure (0.076 / 0.085 at 280 / 320 kg/m³). Studs at BR 443’s default 15%, in the 100mm of wall they occupy.
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| 300mm at λ 0.06 | ≈ 0.20 | Tradical Hemcrete, 275 kg/m³ |
| 300mm at λ 0.07 | ≈ 0.23 | As pre-filled |
| 300mm at λ 0.076 | ≈ 0.25 | Tradical (France), 280 kg/m³ |
| 300mm at λ 0.085 | ≈ 0.27 | Tradical (France), 320 kg/m³; misses the 0.26 limiting value |
| 200mm at λ 0.07 | ≈ 0.34 | Misses the 0.26 limiting value |
| 400mm at λ 0.07 | ≈ 0.17 | Meets 0.18 |
| 300mm at λ 0.07, studs not counted | ≈ 0.22 |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
λ is the whole question. Hempcrete’s conductivity rises with density — how hard it is tamped or sprayed, and the binder — and with moisture: declared values run from about 0.06 at 275 kg/m³ to 0.085 at 320 kg/m³, and Vicat’s data sheet advises adding 20–30% to dry values for the humidity of the air. IsoHemp’s certified design values for its blocks (λUi, UBAtc approval ATG 3169) are 0.071 and 0.080, so U-Monkey’s 0.07 sits at the good end. The timber frame barely matters: the studs (λ 0.13) are only about twice as conductive as the hempcrete round them, so counting them adds about 0.007. What hempcrete brings beyond its U-value is moisture buffering and a vapour-open wall, so keep the finishes lime-based.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a hempcrete wall (hemp-lime)?
A 300mm cast hempcrete wall round a timber frame, lime-rendered outside and lime-plastered inside, has a U-value of about 0.23 W/m²K at λ 0.07 — inside the 0.26 limiting value for a new wall but short of the 0.18 notional value. The often-quoted 0.20 for 300mm needs λ 0.06, the figure given for Tradical Hemcrete at 275 kg/m³; denser mixes declared at 0.076–0.085 give 0.25–0.27, and the 0.27 misses the limit. 400mm at λ 0.07 gives about 0.17.
Is 300mm of hempcrete enough for building regulations?
It depends on the λ the mix can show in service. At λ 0.07, 300mm gives about 0.23 W/m²K, inside the 0.26 limiting value for a new wall (Approved Document L, Table 4.1); at 0.085, a denser mix, it gives about 0.27 and misses, and some makers advise adding 20–30% to dry λ values for the humidity of the air. So use the declared design value for your mix, not a dry laboratory figure — or build thicker: 400mm gives about 0.17 at λ 0.07. Either way 300mm is short of the 0.18 the notional dwelling uses, so the rest of the house has to make that up in the SAP calculation; for an extension, where each new wall should meet 0.18 (Table 4.2), 300mm misses even at λ 0.06 (about 0.20): it takes about 385mm at λ 0.07, or about 335mm at 0.06.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.