A warm flat roof on a 150mm concrete slab needs about 150mm of foil-faced PIR (λ 0.022) for the 0.15 W/m²K Approved Document L sets for a new roof on an existing home — laid in two staggered layers and held with telescopic fasteners, or bonded. As 2 × 75mm it gives 0.14; the same 150mm in a single layer gives 0.1507, which shows as 0.15 but misses, because BR 443’s default air-gap correction (level 1) applies to a single layer of butt-jointed boards, and none (level 0) to two staggered layers. Plain screws count too: five galvanised ones per m² through both layers take the two-layer roof to 0.164, which misses. 160mm in one layer meets it (0.142), and the 0.16 for a new home takes about 140mm in two layers (0.151). The slab itself adds almost nothing: 200mm of concrete instead of 150mm changes the U by 0.0005.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- 1.5mm PVC single-ply membrane (Bauder Thermofol U 15, sd 30m)
- 2 × 75mm foil-faced PIR roof board (λ 0.022), joints staggered, held with telescopic tube fasteners (5 per m²)
- Bitumen air and vapour control layer, fully bonded to the deck
- 150mm reinforced concrete slab
- 13mm plaster
Foil-faced PIR at λ 0.022: Unilin Thin-R FR/ALU (NSAI Agrément 23/0436) in U-Monkey’s library; any foil-faced flat-roof board at 0.022 gives the same. The boards are held with telescopic tube fasteners, 5 per m² (steel recessed at least half the fixing length, no more than 15 per m²), which BR 443 §4.8.3 exempts from the fixings correction; bonded boards give the same. Fixed as Unilin’s NSAI table assumes — five 4.8mm galvanised screws per m² through both layers — the same roof is 0.164 and misses 0.15; with stainless screws it is 0.149. Stone wool: ROCKWOOL HardRock Multi-Fix DD (λ 0.039). The link opens as a new roof on an existing home, judged against Approved Document L’s 0.15 (2021 edition, Table 4.2); a new home’s roof is 0.16 (Table 4.1).
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| 100mm PIR, one layer | ≈ 0.22 | |
| 120mm, one layer | ≈ 0.18 | Misses 0.18: 0.184 |
| 140mm, one layer | ≈ 0.16 | Misses 0.16: 0.1604 |
| 150mm, one layer | ≈ 0.15 | Shows 0.15 but misses it: 0.1507 |
| 160mm, one layer | ≈ 0.14 | Meets 0.15 |
| 150mm as 2 × 75mm, joints staggered | ≈ 0.14 | As pre-filled: two layers take air-gap level 0, and telescopic fasteners no correction |
| 2 × 75mm, 5 galvanised screws per m² through both layers | ≈ 0.16 | Misses 0.15 (0.164): fixed as Unilin’s NSAI table assumes |
| 2 × 75mm, 5 stainless screws per m² | ≈ 0.15 | Meets 0.15, just (0.149) |
| 180mm as 2 × 90mm | ≈ 0.12 | |
| 150mm in one layer, 5 galvanised screws per m² through it | ≈ 0.17 | The screws add 0.022 |
| 150mm in one layer, 5 stainless screws per m² | ≈ 0.16 | They add 0.008 |
| 150mm in one layer, telescopic tube fasteners | ≈ 0.15 | Steel recessed at least half the fixing length, up to 15 per m²: no correction (BR 443 §4.8.3) |
| 150mm in one layer on a 200mm slab | ≈ 0.15 | The deck barely matters |
| Stone wool (λ 0.039), 150 + 60mm | ≈ 0.18 | Meets 0.18 (a non-domestic flat roof) |
| Stone wool, 150 + 100mm | ≈ 0.15 | Misses 0.15 by a hair (0.1501); ROCKWOOL’s table gives 150 + 105mm |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
Thickness, and whether it goes down in one layer or two. BR 443 (§4.8.1) adds an air-gap correction of level 1 to a single layer of boards — about 0.009 here — unless the joints are lapped or sealed or the boards are dimensionally tight to 5mm, and level 0 to double-layer insulation, so two staggered layers of 75mm beat one of 150mm. Fixings are the other lever. On a concrete deck the boards are bonded, or held with telescopic fasteners whose steel is recessed at least half the fixing length, which need no correction at up to 15 per m² (BR 443 §4.8.3); five galvanised screws per m² straight through 150mm of PIR add 0.022, stainless ones 0.008. The deck hardly matters: 200mm of reinforced concrete (λ 2.3) instead of 150mm improves the U by 0.0005, and a 50mm screed laid to falls by about 0.001 — just enough to take a single 150mm layer from 0.1507 to 0.1497. Makers’ and building-control tables are worked to two decimal places with no air-gap correction: Unilin’s NSAI certificate for FR/ALU on concrete (23/0436) puts 160mm with galvanised fixings, or 150mm with stainless, at 0.15, and U-Monkey reproduces both on that basis; a Hertfordshire building-control guide lists 150mm for 0.15. Stone wool (λ 0.039; A2-s1, d0) needs about 255mm: ROCKWOOL’s table for HardRock Multi-Fix gives 150 + 105mm for 0.15.
Condensation risk with a warm roof on concrete
For the pre-filled roof, U-Monkey’s free BS EN ISO 13788 check finds a trace of seasonal condensation under the PVC membrane — a peak of 2.1 g/m² in February — that evaporates in summer: a conditional pass, which holds as long as the vapour values are not all at the unfavourable ends of their tested ranges at once. The bitumen vapour control layer is the one to rely on — the boards’ foil is broken at every joint — so it has to be fully bonded and sealed at laps and upstands, and a new slab or screed can only dry downwards once it is on, so let it dry first.
Stone wool is vapour-open, which puts all the load on that layer: with U-Monkey’s generic bitumen vapour control layer (sd 90m) the 250mm stone-wool roof fails, with about 7 g/m² of condensate still there at the end of the year, so enter the declared value of the layer you will use before relying on it.
Opens pre-filled. The condensation verdict sits just under the U-value — tap it for the full month-by-month check, the surface-mould (fRsi) check included. If it isn’t a pass, How to fix it tests the usual remedies on your build-up — a vapour control layer, a vapour-open underlay, a ventilated void, a warm deck — and applies the one you pick in a tap, with Undo.
Need it in writing for Building Control? The full condensation risk analysis report is £25 +VAT (£30 inc VAT), or included on Monkey Pro Unlimited — see an example report (PDF), or read what building control expects the analysis to show.
It is a screening to BS EN ISO 13788 (the Glaser method), honestly labelled as one: it does not model air leakage, rain or moisture stored in materials, so for high-risk or heritage constructions a full hygrothermal simulation (BS EN 15026) is the right next step. Figures above use the app’s defaults — Manchester (Ringway) climate, humidity class 3 (dwellings with high or unknown occupancy), a 1-in-10 design year and, on a roof, the surface taken 2 K below the air for night-sky cooling — so pick your nearest weather station for your own build-up: the result can change from one station to another.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a warm flat roof on a concrete deck?
A warm flat roof on a 150mm concrete slab needs about 150mm of foil-faced PIR (λ 0.022) for the 0.15 W/m²K Approved Document L sets for a new roof on an existing home — laid in two staggered layers and held with telescopic fasteners, or bonded. As 2 × 75mm it gives 0.14; the same 150mm in a single layer gives 0.1507, which shows as 0.15 but misses, because BR 443’s default air-gap correction (level 1) applies to a single layer of butt-jointed boards, and none (level 0) to two staggered layers. Plain screws count too: five galvanised ones per m² through both layers take the two-layer roof to 0.164, which misses. 160mm in one layer meets it (0.142), and the 0.16 for a new home takes about 140mm in two layers (0.151). The slab itself adds almost nothing: 200mm of concrete instead of 150mm changes the U by 0.0005.
Can PIR go on the flat roof of a block of flats over 18m?
Yes, on the roof itself. Regulation 7(2) of the Building Regulations 2010 requires materials in the external walls and “specified attachments” of a relevant building — one with a storey at least 18m above ground containing dwellings, an institution or rooms for residential purposes — to be Euroclass A2-s1, d0 or A1. A flat roof isn’t an external wall, so that doesn’t reach it, and regulation 7(3)(b) makes clear that even the parts of a roof connected to an external wall are exempt, unless pitched at more than 70° beside a space people use. A balcony is a specified attachment, so it is caught; a terrace over a heated room is a grey area to settle with building control. The roof covering still has to meet Approved Document B’s requirements for external fire performance.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full flat roof U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.