Insulating a flat garage roof from inside as part of a garage conversion — 100mm of PIR between 150mm joists, leaving a 50mm ventilated gap under the deck, and 72.5mm of PIR insulated plasterboard (60mm PIR) under the joists with its joints taped — gives a U-value of about 0.16 W/m²K: the 0.16 Approved Document L asks of a roof kept in a garage conversion (paragraph 4.12(b), Table 4.3), and the figure Celotex’s data sheet gives for it. 150mm of PIR between the joists alone, a common specification, reaches only 0.22, because the joists bridge it through its full depth. Building control guides usually prefer a warm deck where the roof is being re-covered anyway: 150mm of PIR over the deck gives 0.14.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- Existing felt on an 18mm deck: outside the ventilated gap, not counted
- 50mm ventilated gap under the deck, cross-ventilated
- 100mm PIR between 150mm joists at 400mm centres (11.7% timber)
- 72.5mm PIR insulated plasterboard (60mm PIR + 12.5mm board) under the joists, joints taped as the vapour control layer
Joists at 400mm centres taken at 11.7% timber, the figure on Celotex’s Flat Roofing Application Data Sheet “Garage Conversion – Between and Under Joist” (November 2018); BR 443’s general rule, width over spacing plus 0.01 (12.75% for 47mm joists), gives 0.1605 for the pre-filled roof, a whisker over 0.16, so 65mm under the joists (0.155) is the specification with a margin; insulated plasterboard entered as PIR (λ 0.022) and 12.5mm plasterboard. Everything outside the ventilated gap is disregarded (BS EN ISO 6946 §6.9.4). Warm-deck rows: felt, PIR and a polythene vapour control layer on the old 18mm deck, the joist void below unventilated. The pre-filled link opens as an upgraded element.
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| As it is: felt and deck on empty joists, plasterboard ceiling | ≈ 1.83 | Far worse than the 0.35 threshold |
| 150mm PIR between 150mm joists only, 50mm vented gap above (a common spec) | ≈ 0.22 | The joists bridge it: misses 0.16 |
| 100mm PIR between + 50mm PIR under the joists | ≈ 0.17 | Celotex: 0.17 |
| 100mm between + 60mm under | ≈ 0.16 | As pre-filled (0.159; 0.1605 at BR 443’s 12.75%); Celotex: 0.16 |
| 100mm between + 65mm under | ≈ 0.15 | Celotex: 0.15 |
| 175mm joists: 120mm between + 50mm under | ≈ 0.15 | Celotex: 0.15 |
| Warm deck instead: 140mm PIR over the deck, joists left empty | ≈ 0.15 | Meets 0.16 (0.152) |
| Warm deck: 150mm PIR over the deck | ≈ 0.14 | Meets the 0.15 for a new roof too |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
The joists decide how much the between-joist insulation is worth: they run through its full depth (11.7% at 400mm centres on Celotex’s sheet), so 150mm of PIR between them only reaches 0.22, while 100mm between plus a continuous 60mm under them reaches 0.16 — the layer under the joists covers the timber. The gap above the insulation is the other rule: a cold flat roof needs at least 50mm of ventilated space under the deck, cross-ventilated (Celotex asks for “a 50mm minimum ventilation gap above any original insulation”), which is why only 100mm of PIR fits between 150mm joists. Everything above that gap — deck and felt — is disregarded, as BS EN ISO 6946 does for layers outside a well-ventilated air space. Celotex’s garage-conversion data sheet gives, for 150mm joists with 100mm between, 0.19, 0.17, 0.16 and 0.15 with 40, 50, 60 and 65mm of PIR in the insulated plasterboard below, which U-Monkey reproduces. The regulations make the target: a garage roof kept in a conversion is a retained element (Approved Document L paragraph 4.12(b)), to be upgraded to 0.16 if it is worse than 0.35 (Table 4.3), with a lesser standard allowed where the frame’s load-bearing capacity or the upstand heights prevent it (note 4); a new or rebuilt roof is a new element at 0.15 (Table 4.2). Building control guides such as CNC’s say that “a warm roof construction is the best option” where it can be done — insulation over the deck, the void below left unventilated — and BS 6229, as IKO summarises it, no longer recommends cold decks.
Condensation risk in a converted garage roof
A ventilated cold flat roof is one of the constructions BS 5250:2021 covers with prescriptive guidance rather than a calculation, so U-Monkey’s free BS EN ISO 13788 check reports the pre-filled roof as outside a calculation’s scope, with the Glaser result (no interstitial condensation in any month) shown for information. The guidance is the ventilated gap above the insulation — open at both ends, which is hard where the joists run across a garage — and a continuous, taped vapour control layer at the ceiling.
The warm-deck rows are calculated, and they show the vapour control layer has to suit the membrane: with polythene under a bitumen felt, the check finds condensate building up (3.5 g/m² still there at the end of the year). Under a felt or bitumen membrane, use a high-performance vapour control layer, as the warm flat roof page explains.
Opens pre-filled. The condensation verdict sits just under the U-value — tap it for the full month-by-month check, the surface-mould (fRsi) check included. If it isn’t a pass, How to fix it tests the usual remedies on your build-up — a vapour control layer, a vapour-open underlay, a ventilated void, a warm deck — and applies the one you pick in a tap, with Undo.
Need it in writing for Building Control? The full condensation risk analysis report is £25 +VAT (£30 inc VAT), or included on Monkey Pro Unlimited — see an example report (PDF), or read what building control expects the analysis to show.
It is a screening to BS EN ISO 13788 (the Glaser method), honestly labelled as one: it does not model air leakage, rain or moisture stored in materials, so for high-risk or heritage constructions a full hygrothermal simulation (BS EN 15026) is the right next step. Figures above use the app’s defaults — Manchester (Ringway) climate, humidity class 3 (dwellings with high or unknown occupancy), a 1-in-10 design year and, on a roof, the surface taken 2 K below the air for night-sky cooling — so pick your nearest weather station for your own build-up: the result can change from one station to another.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a garage conversion roof (flat roof insulated from below)?
Insulating a flat garage roof from inside as part of a garage conversion — 100mm of PIR between 150mm joists, leaving a 50mm ventilated gap under the deck, and 72.5mm of PIR insulated plasterboard (60mm PIR) under the joists with its joints taped — gives a U-value of about 0.16 W/m²K: the 0.16 Approved Document L asks of a roof kept in a garage conversion (paragraph 4.12(b), Table 4.3), and the figure Celotex’s data sheet gives for it. 150mm of PIR between the joists alone, a common specification, reaches only 0.22, because the joists bridge it through its full depth. Building control guides usually prefer a warm deck where the roof is being re-covered anyway: 150mm of PIR over the deck gives 0.14.
What U-value does a garage conversion roof need?
In England, 0.16 W/m²K for a flat garage roof that is kept and upgraded: Approved Document L treats elements retained in a garage conversion as upgrades (paragraph 4.12(b)) and asks for 0.16 where the roof is worse than 0.35 (Table 4.3). If the roof is rebuilt, the new roof needs 0.15 (Table 4.2). From inside, 100mm of PIR between 150mm joists with 72.5mm insulated plasterboard below meets 0.16 on Celotex’s figures, and 77.5mm (65mm of PIR) leaves a margin; a warm deck with 150mm of PIR over the existing deck meets 0.15.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full flat roof U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.