A garden room roof built as a warm deck — 100mm of PIR above an 18mm OSB deck, under EPDM, with a vapour control layer and a plasterboard ceiling — has a U-value of about 0.20 W/m²K; 120mm gives about 0.17 and 75mm about 0.26. Many garden rooms put the PIR between the joists instead, under an EPDM-covered deck, which is cheaper and lower: 100mm that way gives about 0.27, because the joists bridge it. That cold deck build-up is the one BS 6229:2018 (since revised) said is not now recommended, and U-Monkey’s condensation check reports it as a cold deck — the warm deck is the better roof for a room that will be heated.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- EPDM waterproofing
- 100mm PIR above the deck
- Vapour control layer
- 18mm OSB deck
- 150mm joists (12% timber), unventilated void
- 12.5mm plasterboard
Joists at 12%, the void between them unventilated. In England and Wales, detached (stand-alone) garden rooms of under 50m² that are not dwellings are outside the energy efficiency requirements (Building Regulations 2010, regulation 21(3)(d)), so no U-value is required; the figures are for comparing roofs.
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| 50mm PIR warm deck | ≈ 0.36 | |
| 75mm PIR warm deck | ≈ 0.26 | 0.259 |
| 100mm PIR warm deck | ≈ 0.20 | As pre-filled |
| 120mm PIR warm deck | ≈ 0.17 | |
| 75mm PIR between the joists, EPDM on the deck (cold deck, unventilated) | ≈ 0.33 | U-Monkey’s check: cold deck |
| 100mm PIR between the joists (cold deck, unventilated) | ≈ 0.27 | U-Monkey’s check: cold deck |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
Where the insulation goes matters as much as how much. Above the deck it is continuous; between the joists it is bridged by them (12% here), so 100mm between the joists (0.27) does about as well as 75mm above the deck (0.26). The bigger difference is the deck’s temperature. In a warm deck the OSB sits inside the insulation, at about room temperature; in a cold deck it sits outside it, at about 2 °C in U-Monkey’s check for a February in Manchester, well below the room air’s dew point, so any warm air that gets past the ceiling condenses on it. BS 5250:2021 asks for a cold deck to have a ventilated void at least 50mm deep above the insulation, with cross-ventilation equal to a continuous 25mm opening on each side, and a sealed vapour control layer; a garden room’s roof is rarely deep enough to give the void and still insulate well, which is why the warm deck is the sound choice.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a garden room (garden office) roof?
A garden room roof built as a warm deck — 100mm of PIR above an 18mm OSB deck, under EPDM, with a vapour control layer and a plasterboard ceiling — has a U-value of about 0.20 W/m²K; 120mm gives about 0.17 and 75mm about 0.26. Many garden rooms put the PIR between the joists instead, under an EPDM-covered deck, which is cheaper and lower: 100mm that way gives about 0.27, because the joists bridge it. That cold deck build-up is the one BS 6229:2018 (since revised) said is not now recommended, and U-Monkey’s condensation check reports it as a cold deck — the warm deck is the better roof for a room that will be heated.
Warm or cold deck for a garden room roof?
Warm. The cold deck — insulation between the joists, waterproofing straight onto the deck above them — is the build-up BS 6229:2018 (revised in 2025) noted is not now recommended, because the deck is cold and any room air that reaches it condenses, and BS 5250:2021 only accepts it with a ventilated void at least 50mm deep above the insulation, cross-ventilated on both sides, and a sealed vapour control layer. Unventilated, U-Monkey’s condensation check reports it as a cold deck, outside the scope of a calculation. A warm deck with 100mm of PIR above the deck gives about 0.20 W/m²K and keeps the deck at room temperature; its check is a conditional pass, with a few grams of seasonal condensation under the waterproofing.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full flat roof U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.