A suspended timber floor over an unheated cellar — 140mm of Rockwool Flexi between 175mm joists, a breathable membrane under it and a plasterboard ceiling to the cellar — has a U-value of about 0.26 W/m²K taken as if it faced outside air, and about 0.21 with the cellar counted the way BS EN ISO 13370 §7.4 counts an unheated basement: through its floor and walls to the ground, its walls above ground, and its ventilation. That is for a mid-terrace front cellar of 18m² with 4m of wall to the outside, 1.8m deep, at the standard’s default of 0.3 air changes an hour, the least cautious choice; at the 3 an hour SAP and BR 443 assume for an unheated space of unknown airtightness it is 0.23. The cellar matters most before the floor is insulated: bare boards over it read 2.64 taken as outside air, but 0.70–1.2 with the cellar counted, depending mostly on how draughty it is.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- (The unheated cellar below: 18m², 4m of exposed wall, 1.8m deep, the floor 0.5m above ground, 0.3 air changes an hour — BS EN ISO 13370 §7.4)
- 12.5mm plasterboard ceiling to the cellar
- Windtight vapour-open membrane stapled to the joists
- 35mm air space between the joists
- 140mm Rockwool Flexi slab between 175mm joists at 400mm centres (10.8% timber, BR 443’s figure for floors), tight to the boards
- 22mm softwood floorboards
The cellar is counted with U-Monkey’s “unheated cellar” option under “On the other side”: BS EN ISO 13370 §7.4 as the Passive House Institute and the Home Energy Model’s reference code set it out, with 0.3 air changes an hour and the cellar’s volume A(h + z) by default, and the floor above taken with the inside surface resistance 0.17 on both faces, as BR 443 §9.2 does for a suspended deck. The cellar here: 330mm brick walls (R 0.43), an uninsulated floor, sand or gravel (λ 2.0). The pre-filled link opens as an upgraded floor with the cellar counted; choose “Outside air” for the exposed figure.
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| Taken as outside air (RdSAP’s convention, and the cautious case) | ≈ 0.26 | RdSAP treats a semi-exposed floor as fully exposed |
| The cellar counted, 0.3 air changes an hour (the default) | ≈ 0.21 | As pre-filled |
| The cellar counted, 1 air change an hour (small vents) | ≈ 0.22 | |
| The cellar counted, 3 air changes an hour (open vents, a coal hole) | ≈ 0.23 | SAP’s default for an unheated space of unknown airtightness |
| Before: bare boards on joists, no ceiling, as exposed | ≈ 2.64 | |
| Before: bare boards, the cellar counted | ≈ 0.70 | 0.704; 0.89 at 1 air change an hour, 1.21 at 3 |
| Uninsulated, plasterboard ceiling under the joists, the cellar counted | ≈ 0.58 | 1.43 taken as outside air |
| 100mm mineral wool quilt between the joists, the cellar counted | ≈ 0.26 | Misses the 0.25 for a renovated floor (0.263) |
| 160mm wood-fibre batts (STEICOflex 036), the cellar counted | ≈ 0.19 | |
| 140mm slab + 25mm PIR under the joists, the cellar counted | ≈ 0.16 | |
| End terrace: 8.5m of exposed cellar wall, the cellar counted | ≈ 0.22 | |
| A whole-house cellar, 50m² with 30m of exposed wall (P/A 0.6), the cellar counted | ≈ 0.23 |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for. Rows that count the cellar add it as BS EN ISO 13370 §7.4 does for an unheated basement — its floor and walls to the ground, its walls above ground and its ventilation — which the calculator applies under “On the other side” → “An unheated cellar or basement”.
What changes the number
There are two ways to count the cellar that give an answer, and they differ. BS EN ISO 13370 §7.4 treats an unheated basement as a space that loses heat through its floor and walls to the ground, through its walls above ground to outside air, and by ventilation: 1/U = 1/Uf + A/(A·Ubf + z·P·Ubw + h·P·Uw + 0.33·n·V), where Uf is the floor above with an inside surface resistance on both faces — U-Monkey’s “unheated cellar” option, which needs the cellar’s area A, exposed perimeter P, depth z, the height of the floor above ground h and its air change rate n. SAP 10.2’s general formula for an unheated space (formula 4) leaves ground floors out, so it can’t represent a cellar, and SAP points to BS EN ISO 13370 for basements; RdSAP treats the floor as exposed — the cautious figure. The cellar’s numbers then matter: P counts only the cellar wall with outside ground or air behind it — U-Monkey’s reading leaves out party walls to a neighbour’s cellar and the wall to the ground under the rest of the house — so an end-terrace cellar (8.5m) does worse than a mid-terrace one (4m); and the air change rate runs from the standard’s default of 0.3, the least cautious figure, to the 3 an hour SAP and BR 443 take when an unheated space’s airtightness isn’t known (SAP Table 3.5 gives 0.5 for well-sealed spaces, 1 with small vents, 10 with many openings). A floor over a cellar is a thermal element — it separates the house from an unconditioned space (regulation 2(3)) — so insulating more than half of it brings in Approved Document L’s 0.25 for a renovated floor (Table 4.3), with a lesser standard where meeting it would cause problems with adjoining floor levels (note 8) and the general 0.7 backstop (paragraph 4.13). Heat the cellar or open it to the house and it becomes part of the dwelling: then the basement floor and cellar wall pages apply.
Condensation and damp over a cellar
U-Monkey’s free BS EN ISO 13788 check keeps outside air beneath the floor — colder than any cellar, so the cautious case — and gives the pre-filled floor a conditional pass: no interstitial condensation in any month, as long as the floorboards’ vapour resistance factor is at least μ 30 (μ 50 used, an assumed value for softwood). The membrane under the insulation should be windtight but vapour-open, so the floor can dry downwards.
Insulating the cellar’s ceiling also makes the cellar colder, so its air will be damper and the joists’ lower edges and their bearings sit on the cold side of the insulation: keep the cellar’s vents and gratings open, deal with any damp in it first, and lag pipes running under the insulated floor, as Ecological Building Systems’ guide advises.
Opens pre-filled. The condensation verdict sits just under the U-value — tap it for the full month-by-month check, the surface-mould (fRsi) check included. If it isn’t a pass, How to fix it tests the usual remedies on your build-up — a vapour control layer on the warm side, a more vapour-open layer on the cold side, more insulation to warm the inside surface — and applies the one you pick in a tap, with Undo.
Need it in writing for Building Control? The full condensation risk analysis report is £25 +VAT (£30 inc VAT), or included on Monkey Pro Unlimited — see an example report (PDF), or read what building control expects the analysis to show.
It is a screening to BS EN ISO 13788 (the Glaser method), honestly labelled as one: it does not model air leakage, rain or moisture stored in materials, so for high-risk or heritage constructions a full hygrothermal simulation (BS EN 15026) is the right next step. Figures above use the app’s defaults — Manchester (Ringway) climate, humidity class 3 (dwellings with high or unknown occupancy), a 1-in-10 design year and, on a roof, the surface taken 2 K below the air for night-sky cooling — so pick your nearest weather station for your own build-up: the result can change from one station to another.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a floor over an unheated cellar?
A suspended timber floor over an unheated cellar — 140mm of Rockwool Flexi between 175mm joists, a breathable membrane under it and a plasterboard ceiling to the cellar — has a U-value of about 0.26 W/m²K taken as if it faced outside air, and about 0.21 with the cellar counted the way BS EN ISO 13370 §7.4 counts an unheated basement: through its floor and walls to the ground, its walls above ground, and its ventilation. That is for a mid-terrace front cellar of 18m² with 4m of wall to the outside, 1.8m deep, at the standard’s default of 0.3 air changes an hour, the least cautious choice; at the 3 an hour SAP and BR 443 assume for an unheated space of unknown airtightness it is 0.23. The cellar matters most before the floor is insulated: bare boards over it read 2.64 taken as outside air, but 0.70–1.2 with the cellar counted, depending mostly on how draughty it is.
Why does a floor over a cellar have three different U-values?
Because the cellar can be counted two ways, and the second depends on how draughty the cellar is. Taken as outside air — RdSAP’s convention and the cautious one — the pre-filled floor is 0.26 W/m²K. Counted as BS EN ISO 13370 §7.4 counts an unheated basement, with its losses to the ground and its ventilation, it is 0.21 for a typical mid-terrace front cellar at the standard’s default ventilation, rising to 0.23 at the 3 air changes an hour SAP assumes when it isn’t known. SAP’s own formula for unheated spaces leaves the ground out and can’t be used for a cellar. The difference is biggest before insulating: bare boards read 2.64 as exposed and 0.70–1.2 with the cellar counted — which matters where a floor kept in a conversion is judged against the 0.70 threshold (Approved Document L paragraph 4.12(b)).
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Different build-up? See the full floor U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.