A 9-inch solid brick wall (about 2.1 W/m²K) with 140mm of render-carrying wood-fibre board (STEICO Protect M, λ 0.040) and a lime render system has a U-value of about 0.26 W/m²K with the board’s fixings counted, meeting the 0.30 Approved Document L sets for an upgraded wall. 120mm meets it too, at 0.297 (shown as 0.30), and 120mm of STEICO’s Protect L (λ 0.037) gives 0.28; 100mm of either falls short. Reaching 0.18 — the value for a new wall in an existing home — takes about 220mm of Protect L. Wood fibre is thicker than EPS or phenolic for the same figure, and vapour-open, which suits solid masonry.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- 10mm lime render system
- 140mm wood-fibre render board (STEICO Protect M, λ 0.040), mechanically fixed (6 fixings/m²)
- 215mm solid brick (protected by the insulation: λ 0.56)
- 13mm plaster
Boards from U-Monkey’s library: STEICO Protect dry M (λ 0.040) and L (λ 0.037), Gutex Thermowall (λ 0.040). Fixings counted as stainless screws at 6 per m² through the full board depth (BS EN ISO 6946 Annex F). The brick behind the boards is taken as protected, λ 0.56 (BR 443 §7), with its mortar joints counted (§4.2). The pre-filled link opens as an upgraded solid wall, judged against Approved Document L’s 0.30 (2021 edition, Table 4.3).
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| Bare wall: 215mm brick, 13mm plaster | ≈ 2.10 | |
| 100mm STEICO Protect M (λ 0.040) | ≈ 0.34 | Misses 0.30 |
| 120mm Protect M | ≈ 0.30 | Meets 0.30: 0.297 |
| 140mm Protect M | ≈ 0.26 | As pre-filled |
| 160mm Protect M | ≈ 0.23 | |
| 120mm STEICO Protect L (λ 0.037) | ≈ 0.28 | Meets 0.30 |
| 220mm Protect L | ≈ 0.17 | Meets 0.18, the value for a new wall (200mm: 0.182) |
| 140mm Gutex Thermowall (λ 0.040) | ≈ 0.26 | |
| 140mm, fixings left out | ≈ 0.25 | The fixings add about 0.008 |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
The board’s thickness and grade decide the figure: STEICO’s render-carrying boards come as Protect M (λ 0.040, 60–200mm) and Protect L (λ 0.037, 80–240mm), and Gutex Thermowall matches Protect M. The fixings cost more here than through the thicker board on the CLT wall page: BS EN ISO 6946’s correction for a fixing that crosses the whole board grows as the board gets thinner, so at six a square metre they add about 0.008 here, against about 0.005 there — on a real job the number per square metre depends on the wind load and the system’s certificate, so check it. Wood fibre needs up to about 30% more thickness than EPS (λ 0.031–0.038) for the same figure, and nearly twice as much as phenolic board (λ 0.021), which matters at reveals, eaves and verges; in return it is vapour-open, so the brick can still dry outwards, and U-Monkey’s condensation check finds no condensation in any month for any thickness here. External insulation also puts the brick on the warm side: the surface-mould factor goes from 0.58 for the bare wall, a fail, to 0.94.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of wood-fibre external wall insulation (EWI) on a solid wall?
A 9-inch solid brick wall (about 2.1 W/m²K) with 140mm of render-carrying wood-fibre board (STEICO Protect M, λ 0.040) and a lime render system has a U-value of about 0.26 W/m²K with the board’s fixings counted, meeting the 0.30 Approved Document L sets for an upgraded wall. 120mm meets it too, at 0.297 (shown as 0.30), and 120mm of STEICO’s Protect L (λ 0.037) gives 0.28; 100mm of either falls short. Reaching 0.18 — the value for a new wall in an existing home — takes about 220mm of Protect L. Wood fibre is thicker than EPS or phenolic for the same figure, and vapour-open, which suits solid masonry.
What U-value does external wall insulation need to meet?
In England, Approved Document L asks for 0.30 W/m²K when an existing solid wall is insulated (Table 4.3, improved value, under “wall – internal or external insulation”), so far as that is technically, functionally and economically feasible with a simple payback of 15 years or less (paragraph 4.13). Insulating more than half of a wall counts as renovating it, which brings this in (regulation 23). With wood fibre on a 9-inch brick wall that means about 120mm of Protect M or Protect L. A new wall in an existing home — an extension — is held to 0.18 instead (Table 4.2), about 220mm of Protect L. In a conservation area, external insulation may also need planning permission, so check before you start.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.