An existing room-in-roof slope with 100mm rafters, 50mm of quilt between them and a plasterboard ceiling has a U-value of about 0.79 W/m²K. Under an old bitumen felt, a high-resistance underlay, BS 5250 asks for a ventilated gap between the felt and the insulation — usually 50mm — which leaves 50mm of the rafter depth to insulate. With 50mm of PIR there and 100mm of PIR under the rafters the slope reaches about 0.15, inside the 0.16 that Approved Document L sets for a roof being renovated; 75mm under the rafters gives only 0.19. Re-covering the roof with a vapour-permeable underlay lets you fill the rafters instead: 100mm of PIR between and 60mm under reaches 0.16.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- Tiles on battens (ventilated, not counted)
- Bitumen felt underlay, type 1F (not counted)
- 50mm ventilated gap under the felt (not counted)
- 50mm PIR between 100mm rafters (~12% timber)
- 75–100mm PIR under the rafters (continuous)
- Polythene VCL (warm side)
- Plasterboard
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| As built: 50mm quilt between the rafters | ≈ 0.79 | Renovating it brings in Table 4.3’s 0.16; worse than the 0.35 threshold too |
| 50mm PIR between + 50mm under | ≈ 0.24 | Well short of the 0.16 renovation target |
| 50mm PIR between + 75mm under | ≈ 0.19 | Still short of 0.16 |
| 50mm PIR between + 100mm under | ≈ 0.15 | Meets the 0.16 for a renovated roof |
| Vapour-permeable underlay, no gap: 100mm PIR between + 60mm under | ≈ 0.16 | Meets 0.16 (0.159) with 40mm less lost headroom |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
The ventilated gap is what makes this slope hard. BS EN ISO 6946 disregards it and everything above it, so only the insulation inboard of the gap counts, and in shallow rafters that is not much. Every millimetre under the rafters comes off the room — 100mm of PIR and the plasterboard bring the ceiling 112.5mm further in — which is why the underlay matters: replace the old felt with a vapour-permeable one when the roof is re-covered and the full rafter depth can be filled. Either way, BS 5250 expects an air and vapour control layer on the warm side, and U-Monkey’s free condensation check will not pass the slope without one; as pre-filled, with the VCL behind the plasterboard, it finds next to no condensation, a conditional pass that depends on the assumed vapour values, so enter your products’ declared figures. The other parts of a room in the roof — the stud walls, the flat ceiling and the insulation in the eaves voids — are separate elements: model each one.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a room-in-roof sloping ceiling?
An existing room-in-roof slope with 100mm rafters, 50mm of quilt between them and a plasterboard ceiling has a U-value of about 0.79 W/m²K. Under an old bitumen felt, a high-resistance underlay, BS 5250 asks for a ventilated gap between the felt and the insulation — usually 50mm — which leaves 50mm of the rafter depth to insulate. With 50mm of PIR there and 100mm of PIR under the rafters the slope reaches about 0.15, inside the 0.16 that Approved Document L sets for a roof being renovated; 75mm under the rafters gives only 0.19. Re-covering the roof with a vapour-permeable underlay lets you fill the rafters instead: 100mm of PIR between and 60mm under reaches 0.16.
Do I have to reach 0.16 when I insulate a room in the roof?
If the work renovates the roof — stripping the sloping ceiling back to the rafters, for example — Approved Document L Table 4.3 asks for its improved value of 0.16 W/m²K where that is technically, functionally and economically feasible; where it is not, the slope is improved as far as is feasible within a 15-year simple payback. That holds whatever the slope starts from: the table’s 0.35 threshold is for a roof kept in a conversion (paragraph 4.12(b)), and at about 0.79 this one would be upgraded then too. Headroom is usually what limits it: model the options in U-Monkey and agree the spec with building control before you start.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full roof U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.