A 215mm brick cellar wall lined with a cavity drain membrane and 62.5mm PIR insulated plasterboard (50mm of PIR) on dabs has a U-value of about 0.25 W/m²K, for a cellar 2m deep under a typical house whose existing floor is upgraded as well (70mm of PIR under a screed gives about 0.21, inside the 0.25 Approved Document L asks of a retained floor). That is inside the 0.30 Approved Document L asks of a retained wall insulated inside; 40mm of PIR gives about 0.28 and 25mm about 0.35, which misses. The bare wall is about 0.84 — far better than the same brick above ground, because the ground is part of the calculation (BS EN ISO 13370).
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- (The ground: allowed for by BS EN ISO 13370)
- 215mm brick cellar wall
- Studded cavity drain membrane (an 8mm air gap behind it)
- 15mm gap on plaster dabs
- 50mm PIR insulated plasterboard core
- 12.5mm plasterboard facing
Calculated to BS EN ISO 13370 for a heated basement: perimeter 30m, floor area 50m², floor 2.0m below ground, soil λ 2.0, with the floor’s resistance R 3.24 m²K/W (70mm of PIR under a 65mm screed laid over the existing floor, a floor U-value of about 0.21, inside the 0.25 for a retained floor) entered as the app’s floor R. A new floor, as where the cellar is dug out and relaid, should meet Table 4.2’s 0.18 instead: about 90mm of PIR here (0.17), which leaves the wall figures on this page unchanged. The pre-filled link opens as a retained wall being upgraded, judged against Approved Document L’s 0.30 (2021 edition, Table 4.3).
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| Bare cellar wall: 215mm brick, lime plaster | ≈ 0.84 | |
| 25mm PIR board | ≈ 0.35 | Misses 0.30 |
| 40mm PIR | ≈ 0.28 | |
| 50mm PIR | ≈ 0.25 | As pre-filled (0.246) |
| 75mm PIR | ≈ 0.19 | |
| 50mm PIR, cellar floor left uninsulated | ≈ 0.20 | BS EN ISO 13370 links wall and floor |
| 50mm PIR, cellar 2.5m deep | ≈ 0.23 |
Figures computed to BS EN ISO 13370 with BR 443 conventions, exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up and the footprint and depth shown: your products, thicknesses, perimeter, area and ground will move the number, and that's what the calculator is for.
What changes the number
A converted cellar keeps water out by managing it: BS 8102’s Type C protection lets water through the old wall into the studded cavity drain membrane, which carries it to a drainage channel and pump, and the lining goes on the room side of the membrane — on a mesh-faced membrane, insulated plasterboard can be dabbed straight onto it. The ground does a lot of the work, so modest insulation goes a long way, and the result depends on the cellar’s depth, its plan and the floor: BS EN ISO 13370 links the wall and the floor, so insulating the floor raises the wall’s figure (0.20 with the floor left bare). The membrane is vapour-tight, so the room needs heating and ventilation that keep its humidity down, as the membrane makers stress.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a cellar wall when converting a cellar (basement conversion)?
A 215mm brick cellar wall lined with a cavity drain membrane and 62.5mm PIR insulated plasterboard (50mm of PIR) on dabs has a U-value of about 0.25 W/m²K, for a cellar 2m deep under a typical house whose existing floor is upgraded as well (70mm of PIR under a screed gives about 0.21, inside the 0.25 Approved Document L asks of a retained floor). That is inside the 0.30 Approved Document L asks of a retained wall insulated inside; 40mm of PIR gives about 0.28 and 25mm about 0.35, which misses. The bare wall is about 0.84 — far better than the same brick above ground, because the ground is part of the calculation (BS EN ISO 13370).
What U-values does a cellar conversion need?
In England, Approved Document L treats a cellar’s existing walls and floor like those of a loft or garage conversion — retained elements (paragraph 4.12(b)) — so a wall worse than 0.70 should be upgraded to 0.30 if insulated inside, and the floor to 0.25 (Table 4.3), so far as that is technically and functionally feasible with a simple payback of 15 years or less (paragraph 4.13). New elements meet Table 4.2. Both wall and floor are calculated with the ground, to BS EN ISO 13370, which is why thin linings can meet them.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.