A limecrete floor on 150mm of foamed glass aggregate (Ty-Mawr’s Glapor, λ 0.078) has a U-value of about 0.33 W/m²K for a typical floor, with 30m of exposed perimeter to 50m² of area; 200mm gives about 0.27, still short of the 0.25 Approved Document L sets for an upgraded floor, which takes about 225mm (0.2496). The uninsulated solid floor it replaces is about 0.98. Foamed glass is a weaker insulant than PIR or EPS, so these floors are deep, but it carries the slab, doesn’t draw up ground water, and lets the floor be laid without a damp-proof membrane — which is why it is used in old buildings with solid walls.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- 150mm foamed glass aggregate (Glapor, λ 0.078), compacted
- 100mm limecrete slab (not counted in the floor’s resistance: BR 443)
- (Finish — flags, tiles or boards on a lime screed — not included)
BS EN ISO 13370 at U-Monkey’s default floor (30m of exposed perimeter, 50m², P/A 0.6), ground λ 2.0 (sand or gravel), 300mm walls. The limecrete slab is entered as dense concrete, which BR 443 leaves out of a ground floor’s resistance because it conducts much like the ground, so its exact λ makes no difference. The pre-filled link opens as an upgraded existing floor, judged against Approved Document L’s 0.25 (2021 edition, Table 4.3).
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| Before: an uninsulated solid floor | ≈ 0.98 | |
| 100mm foamed glass | ≈ 0.42 | |
| 150mm foamed glass | ≈ 0.33 | As pre-filled; Ty-Mawr’s minimum |
| 200mm foamed glass | ≈ 0.27 | |
| 250mm foamed glass | ≈ 0.23 | Meets the 0.25 for an upgraded floor (225mm just does) |
| 150mm MISAPOR foam glass gravel (λ 0.09) | ≈ 0.36 | U-Monkey’s library value |
| 150mm at a design λ of 0.105 (MISAPOR, German approval) | ≈ 0.39 | |
| 150mm, a larger floor (P/A 0.35) | ≈ 0.28 | |
| 150mm on clay (ground λ 1.5) | ≈ 0.30 |
Figures computed to BS EN ISO 13370 with BR 443 conventions, exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up and the footprint and depth shown: your products, thicknesses, perimeter, area and ground will move the number, and that's what the calculator is for.
What changes the number
Three things decide the figure: the depth of foamed glass, its λ, and the floor’s shape. Ty-Mawr quotes 0.078 for Glapor without saying on what basis; MISAPOR’s European Technical Assessment (ETA-13/0549) gives 0.080 for its 10/75 grade and 0.093 for 10/50 with a moisture factor of 1.2 for use under a slab, and its German approval gives the 10/75 a design value of 0.105. If Ty-Mawr’s figure is a dry one, the same moisture factor (λ 0.094) takes 150mm to about 0.37; at MISAPOR’s 0.105 design value it would be about 0.39. Like any ground floor, a small or narrow one loses more through its edges: the same 150mm gives about 0.28 on a larger floor (P/A 0.35), and clay, which conducts less than the sand or gravel U-Monkey assumes, helps a little (0.30). Ty-Mawr’s minimum system is 250mm deep — 150mm of Glapor and 100mm of limecrete — before the finish, so an old floor usually has to be dug out, and that needs care: the government’s solid-floor guide warns that digging down next to shallow foundations could undermine the wall, and Historic England calls the excavation the principal disadvantage of these systems. Digging out and relaying a whole floor may also count as replacing it rather than renovating it, which in England brings in 0.18 (Approved Document L, paragraph 4.8 and Table 4.2, with a lesser standard where adjoining floor levels make it impractical, note 4) — about 350mm of Glapor — so agree with building control which applies.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a limecrete floor (insulated with foamed glass)?
A limecrete floor on 150mm of foamed glass aggregate (Ty-Mawr’s Glapor, λ 0.078) has a U-value of about 0.33 W/m²K for a typical floor, with 30m of exposed perimeter to 50m² of area; 200mm gives about 0.27, still short of the 0.25 Approved Document L sets for an upgraded floor, which takes about 225mm (0.2496). The uninsulated solid floor it replaces is about 0.98. Foamed glass is a weaker insulant than PIR or EPS, so these floors are deep, but it carries the slab, doesn’t draw up ground water, and lets the floor be laid without a damp-proof membrane — which is why it is used in old buildings with solid walls.
Does a limecrete floor need a damp-proof membrane?
Not in the systems built for it. Ty-Mawr’s Sublime floor leaves the membrane out and relies on the foamed glass beneath the slab, which doesn’t draw water up, so the floor can let ground moisture evaporate. That is the point in an old building: Historic England’s guidance on insulating solid floors notes that a membrane laid across a floor can displace ground moisture to the base of the walls, where it can cause rising damp instead. U-Monkey’s condensation check doesn’t cover ground floors — moisture from the ground is a matter of the floor’s damp design, not interstitial condensation — so take the system maker’s and a conservation specialist’s advice on the details.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Different build-up? See the full floor U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.