A single leaf of 215mm Solar-grade aircrete (λ 0.11) laid on 2–3mm thin joints and rendered has a U-value of about 0.49 W/m²K — nearly twice the 0.26 limiting value for a new dwelling — so a solid aircrete wall needs insulating: 100mm of grey EPS external wall insulation (λ 0.032) takes it to about 0.20, and 150mm to 0.16. The thin joints matter on the bare wall: laid on conventional 10mm mortar joints, the same wall reads 0.59, because BR 443 counts mortar as a bridge whenever the block is far more insulating than the joints. Behind 100mm of external insulation the joints cost only about 0.01.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- 8mm render on the insulation
- 100mm grey EPS external wall insulation (webertherm XM EPS 70 grey, λ 0.032), screw fixings counted
- 215mm H+H Celcon Solar-grade aircrete (λ 0.11) on thin joints (1.9% mortar at λ 0.88)
- 13mm lightweight plaster
The thin joints are entered as a bridge at BR 443 §4.2’s general fraction for 3mm joints around a 630 × 215mm block face (0.019), with its mortar λ (0.88 behind external insulation, 0.94 on a rendered-only wall), because BR 443 has no thin-joint figure; without it, U-Monkey adds its standard 6.7% for 10mm joints. The block is H+H’s Celcon Plus in Solar grade (λ 0.11, the declared maximum on NBS Source, 460 kg/m³). External insulation fixings as U-Monkey’s “EWI screw fixings” preset (6 per m², λ 17, 19.6mm²).
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| Rendered only: 215mm Solar block, thin joints | ≈ 0.49 | Fails the 0.26 limit for a new dwelling |
| Rendered only, 10mm mortar joints instead | ≈ 0.59 | BR 443’s standard 6.7% of joints |
| Rendered only: 300mm Mannok Aircrete Super (λ 0.12), thin joints | ≈ 0.40 | The widest above-ground aircrete block made as standard |
| 215mm Solar + 60mm grey EPS | ≈ 0.26 | Just misses the 0.26 limit (0.261) |
| 215mm Solar + 100mm grey EPS | ≈ 0.20 | As pre-filled: meets 0.26, misses the 0.18 notional |
| 215mm Solar + 120mm grey EPS | ≈ 0.18 | Just over 0.18 (0.181) |
| 215mm Solar + 150mm grey EPS | ≈ 0.16 | Meets the 0.18 notional and the 0.18 for an extension |
| Standard-grade block (λ 0.15) + 100mm grey EPS | ≈ 0.22 | |
| 215mm Solar + 100mm mineral wool EWI (λ 0.036) | ≈ 0.21 | Non-combustible insulation |
| 215mm Solar + 100mm grey EPS, 10mm mortar joints | ≈ 0.21 | The joints cost about 0.01 behind insulation (0.212) |
| 215mm Solar + 100mm grey EPS, fixings left out | ≈ 0.20 | The screws add about 0.006 (0.196 without them) |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
Three things move a solid aircrete wall: the block’s grade, its joints and the insulation added to it. Grades run from about 0.11 (H+H Solar, Thermalite Turbo) through 0.15 (standard) to 0.18 for the high-strength blocks, and most makers stop at 215mm above ground; Mannok makes a 300mm Aircrete Super (λ 0.12) as standard, which still gives only about 0.40 rendered on thin joints (0.48 on 10mm joints) — reaching 0.26 with a block alone would take about 450mm at λ 0.11. The joints are the subtle one. BR 443 §4.2 counts mortar joints as a bridge unless the block and mortar differ by less than 0.1 m²K/W, which aircrete fails by a wide margin, and gives 6.7% of joints for 10mm mortar around a 440 × 215mm block; it says nothing specific about thin-joint work, so the joints here are its general formula at 3mm around H+H’s 630 × 215mm face: 1.9% of the wall, at BR 443’s mortar λ (0.88 behind insulation, 0.94 where the block is only rendered). A thin-joint mortar’s λ is rarely published: a European thin-bed mortar declares 0.76 and Wienerberger’s Porotherm thin-layer mortar (for clay blocks) 1.17, which would move the rendered-only wall by about 0.01 either way and the insulated one by under 0.002. The block λ needs care on a rendered-only wall: BR 443 takes masonry as exposed unless it has external insulation or cladding, and the 0.11 here is the maker’s declared maximum with no stated moisture basis. External insulation is the realistic route — it keeps the block dry and warm, and covers the thin joints, which can’t be raked out to key a render (H+H recommends a stipple bonding coat or a metal lath). Approved Document L sets 0.26 for the walls of a new dwelling (Table 4.1) and 0.18 for a new wall in an existing one (Table 4.2).
Condensation risk in a solid aircrete wall with external insulation
U-Monkey’s free BS EN ISO 13788 check finds no interstitial condensation in any month for the pre-filled wall, and it stays that way with the EPS tested across BS 5250’s published range of vapour resistance: the insulation outside keeps the block warm, and the block is vapour-open. The render does the weathering, so the system’s details at openings and at the base track matter more than the calculation does.
Opens pre-filled. The condensation verdict sits just under the U-value — tap it for the full month-by-month check, the surface-mould (fRsi) check included. If it isn’t a pass, How to fix it tests the usual remedies on your build-up — a vapour control layer on the warm side, a more vapour-open layer on the cold side, more insulation to warm the inside surface — and applies the one you pick in a tap, with Undo.
Need it in writing for Building Control? The full condensation risk analysis report is £25 +VAT (£30 inc VAT), or included on Monkey Pro Unlimited — see an example report (PDF), or read what building control expects the analysis to show.
It is a screening to BS EN ISO 13788 (the Glaser method), honestly labelled as one: it does not model air leakage, rain or moisture stored in materials, so for high-risk or heritage constructions a full hygrothermal simulation (BS EN 15026) is the right next step. Figures above use the app’s defaults — Manchester (Ringway) climate, humidity class 3 (dwellings with high or unknown occupancy), a 1-in-10 design year and, on a roof, the surface taken 2 K below the air for night-sky cooling — so pick your nearest weather station for your own build-up: the result can change from one station to another.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a solid aircrete wall (thin-joint blockwork)?
A single leaf of 215mm Solar-grade aircrete (λ 0.11) laid on 2–3mm thin joints and rendered has a U-value of about 0.49 W/m²K — nearly twice the 0.26 limiting value for a new dwelling — so a solid aircrete wall needs insulating: 100mm of grey EPS external wall insulation (λ 0.032) takes it to about 0.20, and 150mm to 0.16. The thin joints matter on the bare wall: laid on conventional 10mm mortar joints, the same wall reads 0.59, because BR 443 counts mortar as a bridge whenever the block is far more insulating than the joints. Behind 100mm of external insulation the joints cost only about 0.01.
Can a solid aircrete wall meet Building Regulations without insulation?
Not at any thickness the makers produce. 215mm of Solar-grade aircrete (λ 0.11) on thin joints, rendered and plastered, comes to about 0.49 W/m²K, and Mannok’s 300mm Aircrete Super, also on thin joints, about 0.40, against the 0.26 Approved Document L sets for a new dwelling’s walls; 0.26 would need about 450mm of Solar-grade block (λ 0.11). That is why solid aircrete walls are built with external insulation — 100mm of grey EPS gives about 0.20 — or lined inside (H+H’s thin-joint brochure gives 0.24 for a 200mm solid wall with 62.5mm of phenolic insulated plasterboard).
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.