A brick-clad light steel frame wall — 100mm steel C-studs at 600mm centres with mineral wool between them, 80mm of PIR outside the sheathing board and plasterboard inside — has a U-value of about 0.17 W/m²K by the method BR 443 sets for steel, BRE Digest 465. 60mm of PIR gives about 0.20 and 100mm about 0.15, as SCI’s design guide P402 tabulates them; P402 gives 0.18 for the 80mm wall. The steel is thin, but it conducts nearly 400 times better than timber, so BS EN ISO 6946’s plain average is replaced by a weighting, p, that Digest 465 works out from the frame: 0.65 for this wall.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- 102.5mm brick outer leaf
- 50mm cavity
- Breather membrane
- 80mm PIR board, continuous outside the steel
- 12mm cement particle sheathing board
- 100mm steel C-studs at 600mm centres (1.2mm web: 0.2% steel) with 100mm mineral wool slab between
- Polythene VCL
- 15mm plasterboard
Studs entered as BR 443 asks, as a bridged layer: a 1.2mm web at 600mm centres is 0.2% steel (λ 50). U-Monkey’s steel-frame panel supplies the flange width (50mm), the stud centres (600mm) and the stud depth (the bridged layer, 100mm) for Digest 465’s p. Digest 465 was derived from walls of about 0.20–0.45 W/m²K (Passivhaus Trust, 2022), so the app flags results below that range as less certain.
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| 60mm PIR outside the studs | ≈ 0.20 | SCI P402 Table 2.8: 0.20 |
| 80mm PIR outside the studs | ≈ 0.17 | As pre-filled (p 0.65); P402: 0.18 |
| 100mm PIR outside the studs | ≈ 0.15 | P402: 0.15 |
| 80mm PIR, studs at 400mm centres | ≈ 0.18 | More steel, lower p (0.53): 0.1752 |
| 80mm PIR, plain ISO 6946 average instead of Digest 465 | ≈ 0.17 | 0.1747 — not BR 443’s method for steel |
| 80mm PIR, nothing between the studs (warm frame) | ≈ 0.23 | Normal ISO 6946 (p 0.5) |
| Mineral wool between the studs only (cold frame) | ≈ 0.48 | p 0.41: the steel bypasses the wool |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
Most of the work is done by the board outside the steel, which no stud crosses; the wool between the studs is heavily short-circuited, which is why a cold frame — wool between the studs and nothing outside — is so poor. BR 443 (2019) §4.10 sorts steel walls by where the insulation is: outside the studs only is a warm frame and takes the normal ISO 6946 calculation; between them, or between them and outside (a hybrid, like this one), takes BRE Digest 465. Its p depends on how far apart the two ISO 6946 limits are and on the stud depth, centres and flange width, which U-Monkey asks for in the steel-frame panel that appears when a layer carries a steel bridge (here 50mm flanges, 600mm centres, 100mm deep): closer studs mean more steel and a lower p. Note the names: SCI calls this build-up a “warm frame”, where BR 443 calls it a hybrid. Rails, noggings and the brackets that carry cladding add bridging that a single figure cannot show, which is why published figures for similar walls vary.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a light steel frame wall (SFS)?
A brick-clad light steel frame wall — 100mm steel C-studs at 600mm centres with mineral wool between them, 80mm of PIR outside the sheathing board and plasterboard inside — has a U-value of about 0.17 W/m²K by the method BR 443 sets for steel, BRE Digest 465. 60mm of PIR gives about 0.20 and 100mm about 0.15, as SCI’s design guide P402 tabulates them; P402 gives 0.18 for the 80mm wall. The steel is thin, but it conducts nearly 400 times better than timber, so BS EN ISO 6946’s plain average is replaced by a weighting, p, that Digest 465 works out from the frame: 0.65 for this wall.
Why does a steel frame wall need a different calculation?
Because steel conducts so well that the two limits BS EN ISO 6946 averages end up far apart, and the plain average is then no longer reliable. BR 443 (2019) §4.10 therefore uses BRE Digest 465 for cold and hybrid frames: the same two limits, weighted by a factor p instead of half and half. Here that gives a slightly lower U-value than the plain average (0.166 against 0.175); with the wool between the studs only, Digest 465 is the harsher of the two. Only a warm frame, with all the insulation outside the steel, keeps the normal method — including a correction for the fixings that hold that insulation on.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.