A 300mm coat of water reed thatch with a plasterboard ceiling under the rafters has a U-value of about 0.28 W/m²K, taking the λ of 0.09 that Dorset Council’s thatch guidance gives for reed, from CIBSE Guide A; the thatch on its own is about 0.30. Thatch is a good insulator for a roof covering — 450mm of reed, or 350mm of long straw (λ 0.07), gives about 0.19, close to the 0.2 that guidance quotes — but a 300mm coat falls well short of the 0.16 Approved Document L asks of a renovated roof. Over an unused loft, 270mm of quilt at the ceiling gives about 0.15, as in any loft.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- 300mm water reed thatch (λ 0.09) on battens
- 100mm rafter void, unventilated (12% timber)
- 12.5mm plasterboard under the rafters
Thatch λ from Dorset Council’s “Dorset Model” guidance (reed 0.09, straw 0.07, citing CIBSE Guide A); the East Anglian Master Thatchers Association gives the same for water reed and long straw. Rafters at 12%, the rafter void unventilated. The loft row counts everything above the ceiling insulation as one roof-space resistance (BR 443 §8), with the joists at 12.8%. The pre-filled link opens as an existing element.
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| 300mm water reed on its own | ≈ 0.30 | The thatch and its surfaces only |
| 300mm water reed, plasterboard under the rafters | ≈ 0.28 | As pre-filled |
| 350mm water reed | ≈ 0.24 | |
| 450mm water reed | ≈ 0.19 | Dorset Council: 0.2 |
| 350mm long straw (λ 0.07) | ≈ 0.19 | Dorset Council: 0.2 |
| 450mm long straw | ≈ 0.16 | Meets 0.16: 0.155 |
| 300mm reed + 100mm wood-fibre batts between the rafters | ≈ 0.17 | |
| 300mm reed over a loft: 270mm of quilt at the ceiling | ≈ 0.15 | The thatch becomes part of the roof space (R 0.2) |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
The material and the thickness decide it. Water reed is the more conductive thatch (λ 0.09 in the CIBSE figures Dorset Council quotes), long straw and combed wheat reed about 0.07, and a new coat is typically 280–330mm of water reed or 400mm or more of long straw (East Anglian Master Thatchers Association guidance), thinning as it weathers. Under the coat, a room in the roof gains a little from the rafter void and the ceiling, and wood-fibre batts between the rafters take 300mm of reed to about 0.17 — but Historic England’s advice is that insulation at rafter level is “generally neither necessary nor appropriate” under thatch, and that where the roof space isn’t lived in, insulation at ceiling level may be considered. Over a loft, BR 443 gives everything above the ceiling insulation one roof-space resistance from BS EN ISO 6946 Table 9, whose rows are for tiled and sheeted roofs; there is none for thatch, and U-Monkey takes 0.2, the row for a covering with boards or felt under it, which gives 300mm of reed almost no credit — a cautious figure. RdSAP 2012, which does count the thatch, gave 0.35 for an uninsulated thatched roof and 0.12 with 270mm in the loft (Table S9; RdSAP 10 has since replaced it).
Condensation risk under thatch
U-Monkey’s free BS EN ISO 13788 check finds no interstitial condensation in any month in any of the rafter-level rows here. It still rates them “not a pass”, because BS 5250:2021 expects an air and vapour control layer on the warm side of a roof insulated at the slope, and a calculation can’t see the warm, moist room air that leaks up through a ceiling, which is how most moisture gets into a roof. Over a loft it treats the roof as a cold pitched roof, which BS 5250 handles by prescriptive rules instead of a calculation.
What matters most in practice is keeping room air out of the thatch: seal the ceiling’s joints, the loft hatch, pipes and light fittings. A fire barrier over the rafters — Dorset Council’s guidance asks for a 30-minute one on new thatched buildings and extensions within 12m of a boundary — changes both results, so add it as a layer and run the check again. Historic England warns that such a board may leave a ventilated void under the thatch; if that void is ventilated, the thatch sits outside it and counts for nothing in a U-value calculation (about 2.1 for this roof, against about 0.26 with the void sealed), so any insulation meant to count would have to go under the board — and whether to add it at all needs the care Historic England asks for.
Opens pre-filled. The condensation verdict sits just under the U-value — tap it for the full month-by-month check, the surface-mould (fRsi) check included. If it isn’t a pass, How to fix it tests the usual remedies on your build-up — a vapour control layer, a vapour-open underlay, a ventilated void, a warm deck — and applies the one you pick in a tap, with Undo.
Need it in writing for Building Control? The full condensation risk analysis report is £25 +VAT (£30 inc VAT), or included on Monkey Pro Unlimited — see an example report (PDF), or read what building control expects the analysis to show.
It is a screening to BS EN ISO 13788 (the Glaser method), honestly labelled as one: it does not model air leakage, rain or moisture stored in materials, so for high-risk or heritage constructions a full hygrothermal simulation (BS EN 15026) is the right next step. Figures above use the app’s defaults — Manchester (Ringway) climate, humidity class 3 (dwellings with high or unknown occupancy), a 1-in-10 design year and, on a roof, the surface taken 2 K below the air for night-sky cooling — so pick your nearest weather station for your own build-up: the result can change from one station to another.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a thatched roof?
A 300mm coat of water reed thatch with a plasterboard ceiling under the rafters has a U-value of about 0.28 W/m²K, taking the λ of 0.09 that Dorset Council’s thatch guidance gives for reed, from CIBSE Guide A; the thatch on its own is about 0.30. Thatch is a good insulator for a roof covering — 450mm of reed, or 350mm of long straw (λ 0.07), gives about 0.19, close to the 0.2 that guidance quotes — but a 300mm coat falls well short of the 0.16 Approved Document L asks of a renovated roof. Over an unused loft, 270mm of quilt at the ceiling gives about 0.15, as in any loft.
Do I have to insulate a thatched roof when it is re-thatched?
Possibly, but not at any cost. In England, re-thatching adds or replaces a layer of the roof, so doing more than half of it counts as renovating a thermal element (Building Regulations 2010, regulations 2 and 23), which brings in Approved Document L’s 0.16 W/m²K (Table 4.3) where that is technically, functionally and economically feasible with a simple payback of 15 years or less (paragraph 4.13). For a historic or traditional building, Approved Document L adds that energy efficiency should be improved only where it won’t cause long-term deterioration of the fabric or fittings (paragraph 0.10), and listed buildings and those in conservation areas need only meet the standards so far as that won’t unacceptably alter their character or appearance (0.8–0.9). Historic England advises against insulating at rafter level under thatch. Agree the approach with building control, and with the conservation officer where the building is listed.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full roof U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.