A tapered PIR scheme (λ 0.022) falling 1:60 over a 6m run, from 100mm at the outlet to 200mm, on a 150mm concrete deck averages about 0.15 W/m²K (0.147) — within the 0.15 Approved Document L sets for a new roof on an existing home and the 0.16 for a new home. That is for the usual build-up, tapered boards over a flat base board: laid as a single layer of tapered boards it takes BR 443’s default air-gap correction and averages 0.156, which misses 0.15, so start it at 110mm (0.146). The average has to be taken over the area, as BS EN ISO 6946 (Annex E) does, not by averaging the thickness: the thin end loses more heat than the thick end saves, so 80 → 180mm, which averages 130mm, gives 0.170 — not the 0.162 that the average thickness suggests. BS 6229 adds a limit of its own: no point on a heated roof worse than 0.35, which on this deck needs at least 58mm of foil-faced PIR at the thinnest point (59mm as a single layer).
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- 1.5mm PVC single-ply membrane
- Tapered foil-faced PIR (λ 0.022) over a flat base board, 1:60, 100 → 200mm in total over a 6m run (U-Monkey’s tapered option, laid as two layers)
- Bitumen air and vapour control layer
- 150mm reinforced concrete slab
- 13mm plaster
The link opens as a new roof on an existing home, judged against Approved Document L’s 0.15 (2021 edition, Table 4.2), with U-Monkey’s tapered option on (a one-way fall, BS EN ISO 6946:2017 Annex E; tapered boards over a flat base board, so no air-gap correction) and the deck below as flat layers. The condensation check works on one section through the roof, so it is not run on the tapered scheme: the condensation button below opens the thinnest section instead, as a flat 100mm board.
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| 60 → 160mm (1:60 over 6m) | ≈ 0.20 | Thinnest point 0.34, just inside BS 6229’s 0.35 |
| 80 → 180mm | ≈ 0.17 | Thinnest point 0.26; averaging the thickness (130mm) would suggest 0.162 |
| 100 → 200mm | ≈ 0.15 | As pre-filled: 0.147; thinnest point 0.21 |
| 100 → 200mm as one layer of tapered boards | ≈ 0.16 | BR 443’s level 1 air-gap correction: 0.156, misses 0.15; thinnest point 0.22 |
| 110 → 210mm as one layer | ≈ 0.15 | Meets 0.15 (0.146) |
| 120 → 220mm | ≈ 0.13 | |
| 80 → 230mm (1:60 over 9m) | ≈ 0.15 | A longer run lowers the average, but the outlet still sets the thinnest point (0.26) |
| 30 → 130mm | ≈ 0.29 | Fails BS 6229 at the outlet: 0.62 at the thinnest point |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions, the tapered course averaged over its area by BS EN ISO 6946 Annex E (BR 443 §8) — laid over a flat base board, so with no air-gap correction on it unless a row says one layer — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses, fall and layout will move the number, and that's what the calculator is for.
What changes the number
The fall, the run and the thickness at the outlet. A fall of 1:60 adds about 17mm per metre of run, so a 6m run adds 100mm and a 9m run 150mm; the outlet thickness sets the BS 6229 check and much of the average. Bauder’s summary of BS 6229:2025 says the old advice to design for 1:40 to achieve 1:80 has gone: 1:80 is the minimum completed fall on most flat roofs, and a design fall of 1:60 a reasonable starting point in many cases. U-Monkey’s tapered option takes a one-way fall over a rectangle — BS EN ISO 6946’s Annex E formula, U = ln(1 + R₁/R₀)/R₁, with R₀ the total resistance at the thinnest point and R₁ the extra resistance at the thickest — which suits a single-fall roof; hips, valleys and sumps form triangles, which Annex E handles with formulas of their own, and a whole roof is the area-weighted average of its parts, so makers design each scheme to the project. The pre-filled scheme is tapered boards over a flat base board, double-layer insulation, so BR 443 sets its air-gap correction at level 0; a single layer of tapered boards takes level 1, about 0.009 more averaged over the fall (0.156 at 100 → 200mm), and needs 59mm rather than 58mm at the outlet for BS 6229’s 0.35 — U-Monkey’s tapered option asks which it is. Fixings are a correction of their own, which the tapered option leaves to you: telescopic fasteners need none (BR 443 §4.8.3), but five galvanised screws per m² through a 100 → 200mm taper would add about 0.02, stainless ones about 0.01.
Condensation risk with tapered insulation
The thinnest section is the worst case, so that is the one to check. Entered as a flat 100mm board under the membrane — the button below opens it that way — the pre-filled scheme’s outlet gives a conditional pass in U-Monkey’s BS EN ISO 13788 check: about 4 g/m² of seasonal condensation under the membrane in February that evaporates in summer. That link is the outlet section on its own, so the U-value and verdict the app shows with it (0.22, a fail) are the section’s, not the scheme’s 0.147. BS 6229’s 0.35 limit exists for surface condensation at the low points — outlets, gutters and sumps — which is why the thinnest point matters as much as the average.
Opens pre-filled. The condensation verdict sits just under the U-value — tap it for the full month-by-month check, the surface-mould (fRsi) check included. If it isn’t a pass, How to fix it tests the usual remedies on your build-up — a vapour control layer, a vapour-open underlay, a ventilated void, a warm deck — and applies the one you pick in a tap, with Undo.
Need it in writing for Building Control? The full condensation risk analysis report is £25 +VAT (£30 inc VAT), or included on Monkey Pro Unlimited — see an example report (PDF), or read what building control expects the analysis to show.
It is a screening to BS EN ISO 13788 (the Glaser method), honestly labelled as one: it does not model air leakage, rain or moisture stored in materials, so for high-risk or heritage constructions a full hygrothermal simulation (BS EN 15026) is the right next step. Figures above use the app’s defaults — Manchester (Ringway) climate, humidity class 3 (dwellings with high or unknown occupancy), a 1-in-10 design year and, on a roof, the surface taken 2 K below the air for night-sky cooling — so pick your nearest weather station for your own build-up: the result can change from one station to another.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of tapered roof insulation?
A tapered PIR scheme (λ 0.022) falling 1:60 over a 6m run, from 100mm at the outlet to 200mm, on a 150mm concrete deck averages about 0.15 W/m²K (0.147) — within the 0.15 Approved Document L sets for a new roof on an existing home and the 0.16 for a new home. That is for the usual build-up, tapered boards over a flat base board: laid as a single layer of tapered boards it takes BR 443’s default air-gap correction and averages 0.156, which misses 0.15, so start it at 110mm (0.146). The average has to be taken over the area, as BS EN ISO 6946 (Annex E) does, not by averaging the thickness: the thin end loses more heat than the thick end saves, so 80 → 180mm, which averages 130mm, gives 0.170 — not the 0.162 that the average thickness suggests. BS 6229 adds a limit of its own: no point on a heated roof worse than 0.35, which on this deck needs at least 58mm of foil-faced PIR at the thinnest point (59mm as a single layer).
Can you average the thickness of tapered insulation to get its U-value?
No. Heat flows in proportion to 1/R, not to thickness, so the U-value has to be averaged over the area: BS EN ISO 6946 Annex E gives the formulas, and BR 443 (§8) sends tapered layers to it. Averaging the thickness flatters the result — 80 → 180mm of PIR on a concrete deck gives 0.170 by Annex E, against 0.162 from its 130mm average thickness — and Gradient Roofing made the same point in 2016 with a 1:60 scheme for 0.18 that needed 80 → 200mm by the area method, where averaging the thickness said 70 → 190mm would do. Approved Document L judges the area-weighted average; BS 6229 separately caps any point at 0.35.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full flat roof U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.