A steel frame system (SFS) infill wall — 100mm steel studs at 600mm centres with 100mm of ROCKWOOL NyRock Frame Slab 032 between them, 12.5mm Siniat Weather Defence sheathing, and 150mm of NyRock Rainscreen 032 outside behind ventilated cladding — has a U-value of about 0.14 W/m²K before the cladding brackets are counted, and about 0.16 with the χ values certified for one low-conductivity bracket system. BR 443 says brackets that pass through the insulation must be counted: from the bracket system’s own point thermal transmittances (χ) where they exist, or by adding a conservative 0.30 W/m²K where they don’t — which takes the same wall to 0.44 and fails the 0.26 limiting value at any thickness. So the U-value of a rainscreen wall is as much a question of which brackets, and whose numbers, as of insulation.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- Rainscreen cladding (8mm fibre cement) and its ventilated cavity: not counted, BR 443 §4.8.5
- 150mm ROCKWOOL NyRock Rainscreen 032 (λ 0.032), pierced by the cladding brackets (Σχ·n 0.014 W/m²K)
- Breather membrane
- 12.5mm Siniat Weather Defence sheathing board (λ 0.25, A1)
- 100mm steel C-studs at 600mm centres (1.2mm web: 0.2% steel) with 100mm NyRock Frame Slab 032 between them
- Polythene vapour control layer
- 15mm fire-rated plasterboard (modelled as high-density plasterboard)
The brackets are entered as the Passive House Institute component certificate for the BILDA Rainscreen System gives them for heavy (stone) cladding: supporting brackets at 0.12 and 0.20 per m² (χ 0.0353 W/K) and restraining brackets at 0.49 per m² (χ 0.0053 W/K), Σχ·n 0.0139 W/m²K, entered as their mean χ (0.01715 W/K) over 0.81 brackets per m² — use your own system’s figures. The certificate’s χ values were calculated for its reference façade, with 240mm of insulation at λ 0.035, and it was valid to the end of 2025; a bracket’s χ changes with the insulation depth and the wall behind it, so the figures here are an example, not a property of this wall. The steel frame is BRE Digest 465’s hybrid case in U-Monkey’s light steel frame panel (50mm flanges, 600mm centres). The cladding and its ventilated cavity are disregarded and the outside surface resistance becomes 0.13 (BS EN ISO 6946 §6.9.4; BR 443 §4.8.5).
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| No brackets counted (U0): 150mm rainscreen slab | ≈ 0.14 | Where BR 443 does not let you stop: brackets through the insulation must be counted |
| Example certified brackets (Σχ·n 0.014): 100mm rainscreen slab | ≈ 0.20 | Meets the 0.26 limit; misses the 0.18 notional |
| Example certified brackets: 150mm rainscreen slab | ≈ 0.16 | As pre-filled (0.156) |
| Example certified brackets: 200mm rainscreen slab | ≈ 0.13 | |
| Brackets with no calculated χ: BR 443’s +0.30 default, 150mm | ≈ 0.44 | Fails 0.26 — and no thickness of slab can pass with 0.30 added |
| Brackets with no calculated χ: BR 443’s +0.30 default, 200mm | ≈ 0.42 | |
| 150mm studs + 150mm frame slab, 150mm rainscreen, example certified brackets | ≈ 0.14 | |
| Warm frame: nothing between the studs, 150mm rainscreen, example certified brackets | ≈ 0.21 | All the insulation outside the steel: plain ISO 6946, no Digest 465 weighting (BR 443 §4.10) |
| RainScreen Duo (λ 0.035) 150mm instead, example certified brackets | ≈ 0.16 | 0.164 |
| Studs at 400mm centres (0.3% steel), 150mm, example certified brackets | ≈ 0.16 | 0.163 |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
The brackets come first. BR 443 (2019) §4.8.5 says the brackets or rails that fix rainscreen cladding “must be taken into account” where they penetrate the insulation, in one of four ways: a detailed calculation of the whole wall; a linear thermal transmittance for a rail; a point thermal transmittance (χ, W/K) for each bracket, added as U = U0 + Σχ·n with n brackets per m²; or, where no calculated result exists, U0 plus a conservative 0.30 W/m²K. The Annex F fixings correction of BS EN ISO 6946, used for wall ties and screws, is not the method for them. A χ comes from a three-dimensional calculation (BS EN ISO 10211) by the bracket or subframe maker, and how much it adds varies far more than the insulation does: the Passive House Institute’s certificate for the BILDA rainscreen system, for heavy stone cladding, gives Σχ·n 0.0139 W/m²K (the pre-filled figure); ROCKWOOL’s own NyRock Rainscreen 032 tables, modelled in 3-D with FastFrame brackets and 8mm cladding, read 0.18 at 145mm and 0.17 at 160mm, about 0.035 above U-Monkey’s U0; and Hilti’s rainscreen brochure takes one wall from 0.161 without brackets to anywhere between 0.165 and 0.357 with them, depending on the bracket system. The steel studs are BRE Digest 465’s hybrid frame — insulation between and outside the studs — which U-Monkey’s light steel frame panel applies, weighting the upper and lower limits by p; keeping most of the insulation outside the steel keeps the studs warm (“the majority of the insulation should be external”, SCI P283), and the warm frame row, with nothing between the studs, shows the other extreme. Results below about 0.20 sit outside the range of walls Digest 465 was derived from, and the calculator says so. Slab edges, head tracks and window reveals are linear thermal bridges, not part of the U-value — model them in ΨMonkey. And in England, on a relevant building — one with a storey at least 18m above ground that contains dwellings, an institution or rooms for residential purposes — regulation 7(2) of the Building Regulations limits the materials in an external wall to A2-s1,d0 or A1: the mineral wool and the Weather Defence board here qualify; PIR and phenolic rainscreen boards (Kooltherm K15 is C-s2,d0) do not.
Condensation risk in an SFS rainscreen wall
U-Monkey’s free BS EN ISO 13788 check finds no interstitial condensation in any month for the pre-filled wall, and it stays that way with every assumed vapour value tested across its plausible range and the vapour control layer at a third of its rated resistance, one at a time and all together: the polythene layer inside, the vapour-open sheathing (μ 10) and membrane outside, and two-thirds of the insulation outside the steel.
The check is one-dimensional, through the insulation between the studs; the studs themselves and the brackets are two- and three-dimensional effects it cannot see. Keep the vapour control layer continuous and sealed at the head and base tracks and around openings, and keep the bulk of the insulation outside the frame — a cold frame, with wool only between the studs, is where condensation on the steel becomes a risk.
Opens pre-filled. The condensation verdict sits just under the U-value — tap it for the full month-by-month check, the surface-mould (fRsi) check included. If it isn’t a pass, How to fix it tests the usual remedies on your build-up — a vapour control layer on the warm side, a more vapour-open layer on the cold side, more insulation to warm the inside surface — and applies the one you pick in a tap, with Undo.
Need it in writing for Building Control? The full condensation risk analysis report is £25 +VAT (£30 inc VAT), or included on Monkey Pro Unlimited — see an example report (PDF), or read what building control expects the analysis to show.
It is a screening to BS EN ISO 13788 (the Glaser method), honestly labelled as one: it does not model air leakage, rain or moisture stored in materials, so for high-risk or heritage constructions a full hygrothermal simulation (BS EN 15026) is the right next step. Figures above use the app’s defaults — Manchester (Ringway) climate, humidity class 3 (dwellings with high or unknown occupancy), a 1-in-10 design year and, on a roof, the surface taken 2 K below the air for night-sky cooling — so pick your nearest weather station for your own build-up: the result can change from one station to another.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of an SFS infill wall with rainscreen cladding?
A steel frame system (SFS) infill wall — 100mm steel studs at 600mm centres with 100mm of ROCKWOOL NyRock Frame Slab 032 between them, 12.5mm Siniat Weather Defence sheathing, and 150mm of NyRock Rainscreen 032 outside behind ventilated cladding — has a U-value of about 0.14 W/m²K before the cladding brackets are counted, and about 0.16 with the χ values certified for one low-conductivity bracket system. BR 443 says brackets that pass through the insulation must be counted: from the bracket system’s own point thermal transmittances (χ) where they exist, or by adding a conservative 0.30 W/m²K where they don’t — which takes the same wall to 0.44 and fails the 0.26 limiting value at any thickness. So the U-value of a rainscreen wall is as much a question of which brackets, and whose numbers, as of insulation.
What χ value should I use for rainscreen brackets?
The one your bracket or subframe supplier calculates for your brackets, cladding weight and spacing, to BS EN ISO 10211 — normally one χ per bracket type (fixed and sliding points, or supporting and restraining brackets) with the number of each per m², summed as Σχ·n and added to the wall’s U-value (BR 443 §4.8.5(c)). As a sense of scale, the Passive House Institute–certified BILDA system lists χ 0.0353 W/K for its supporting brackets and 0.0053 for its restraining brackets — at 0.32 and 0.49 per m² for stone cladding, 0.0139 W/m²K in all. With no calculated χ, BR 443 §4.8.5(d) adds 0.30 W/m²K, enough on its own to fail Approved Document L’s 0.26 limit. In U-Monkey, enter brackets in the rainscreen layer’s fixings sheet: “Certified χ per fixing or bracket”, or “Rainscreen brackets, no χ” for the default.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.