External wall insulation finished with brick slips on a solid 9-inch brick wall needs about 110mm of grey EPS (Wetherby Epsitherm 70E, λ 0.032) to meet the 0.30 W/m²K Approved Document L asks of an upgraded wall: U-Monkey gives 0.28 with the system’s certified fixings counted (7 per m² at χ 0.004 W/K), and 100mm misses, at 0.31. The BBA certificate’s table puts 100mm at 0.30. Like U-Monkey, it takes the brick behind as protected (λ 0.56), as BR 443 does once a wall has external insulation, and its figures are close to a calculation with no air-gap correction: U-Monkey gives 0.299 on that basis, and adds BR 443’s default correction otherwise. The slips themselves add almost nothing: what sets them apart from render is the finish, the weight and the fixings.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- 15mm brick slips on adhesive, pointed (λ 0.77, as the BBA certificate takes them)
- 110mm Wetherby Epsitherm 70E grey EPS (λ 0.032), 7 fixings per m² at χ 0.004 W/K
- 215mm solid brick (protected by the insulation: λ 0.56)
- 13mm plaster
The slips, the insulation and the fixings follow BBA 14/5137 Product Sheet 1 (Wetherby Epsibrick EWI system; a 2014 issue, read in a council planning file): 15mm brick slips at λ 0.77, Epsitherm 70E λ 0.032 (90E 0.030), seven galvanised fixings per m² at χ 0.004 W/K, entered as certified point thermal transmittances. The brick behind the insulation is taken as protected, λ 0.56 (BR 443 §7), as the certificate takes it, with its mortar joints counted (§4.2); one row shows the exposed 0.77. Mineral wool rows: K Systems’ dual-density slab (λ 0.036) with the same fixings. The pre-filled link opens as an upgraded solid wall.
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| 80mm Epsitherm 70E (λ 0.032) | ≈ 0.36 | |
| 90mm | ≈ 0.33 | The maker’s web page says 90mm meets refurbishment standards “in the majority of cases” |
| 100mm | ≈ 0.31 | Misses 0.30 (0.306); the BBA table’s 100mm has no air-gap correction |
| 110mm | ≈ 0.28 | As pre-filled: meets 0.30 |
| 120mm | ≈ 0.27 | |
| 130mm | ≈ 0.25 | BBA: 130mm for 0.25 |
| 90mm Epsitherm 90E (λ 0.030) | ≈ 0.32 | |
| 100mm Epsitherm 90E | ≈ 0.29 | Meets 0.30 (0.292) |
| 100mm mineral wool (λ 0.036) | ≈ 0.33 | Non-combustible insulation, for taller buildings |
| 120mm mineral wool | ≈ 0.29 | Meets 0.30 (0.292) |
| 140mm mineral wool | ≈ 0.26 | |
| 100mm EPS, fixings left out | ≈ 0.28 | The fixings add 0.028 |
| 100mm EPS, no air-gap correction (the BBA table’s basis) | ≈ 0.30 | Meets 0.30 (0.299); BBA: 0.30 |
| 100mm EPS with the brick at the exposed λ 0.77 | ≈ 0.31 | Misses (0.312): the exposed value is for brick with nothing outside it |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
Brick slips are a finish, not insulation: 15mm of slip on adhesive is worth about R 0.02 m²K/W, the same as a thin render, so the insulation and its fixings set the U-value. The BBA certificate for Wetherby’s Epsibrick system (14/5137 Product Sheet 1) counts seven galvanised fixings per m² at χ 0.004 W/K each, 0.028 on every row, and U-Monkey takes them as certified point thermal transmittances; left out, 100mm reads 0.28. The conventions explain the rest. BR 443 takes solid masonry as protected once it has external insulation, and U-Monkey and the certificate’s table both use protected brick (λ 0.56): the table gives 100mm for 0.30, 130mm for 0.25 and 190mm for 0.18. With the brick protected, BR 443 §4.2 counts its mortar joints (17.3% at λ 0.88, about +0.002), and U-Monkey also adds BR 443’s default air-gap correction (level 1) to the boards; without the correction it gives 0.299, 0.244 and 0.182 for the table’s 100, 130 and 190mm, close to the certificate. Taking the brick at its exposed value (0.77) instead would add about 0.006 at 100mm. 110mm meets 0.30 on any of these bases. Mineral wool (λ 0.036) needs about 120mm, but in England it is the insulation for a relevant building — one with a storey at least 18m above ground that contains dwellings, an institution or rooms for residential purposes: the EPS system is classed B-s1,d0, which regulation 7(2) rules out there, and the mineral wool versions are A2-s1,d0 or A1. The fixing pattern is the system’s own, and “for application to second storey floors and above” the certificate recommends that the designer considers at least one stainless-steel fixing per m² and fire barriers, in line with BRE’s fire guidance for external insulation (BR 135). Planning can be the reason for slips at all: householder permitted development asks for external materials “of a similar appearance” to the existing house (Schedule 2, Part 1, Class A, condition A.3(a)), and in a conservation area permitted development excludes cladding in stone, render, timber, plastic or tiles (A.2(a)), so check with the council; Historic England considers external insulation unlikely to be acceptable on a listed building.
Condensation risk with brick-slip external insulation
U-Monkey’s free BS EN ISO 13788 check finds no interstitial condensation in any month for the pre-filled wall, and it stays that way with the slips, the EPS and the brick each tested across BS 5250’s published range of vapour resistance, one at a time and all together: insulation outside keeps the brick warm. The slip-and-adhesive skin is cementitious and less vapour-open than a lime render, which is why Historic England favours lime renders and rainscreens on traditional walls.
Opens pre-filled. The condensation verdict sits just under the U-value — tap it for the full month-by-month check, the surface-mould (fRsi) check included. If it isn’t a pass, How to fix it tests the usual remedies on your build-up — a vapour control layer on the warm side, a more vapour-open layer on the cold side, more insulation to warm the inside surface — and applies the one you pick in a tap, with Undo.
Need it in writing for Building Control? The full condensation risk analysis report is £25 +VAT (£30 inc VAT), or included on Monkey Pro Unlimited — see an example report (PDF), or read what building control expects the analysis to show.
It is a screening to BS EN ISO 13788 (the Glaser method), honestly labelled as one: it does not model air leakage, rain or moisture stored in materials, so for high-risk or heritage constructions a full hygrothermal simulation (BS EN 15026) is the right next step. Figures above use the app’s defaults — Manchester (Ringway) climate, humidity class 3 (dwellings with high or unknown occupancy), a 1-in-10 design year and, on a roof, the surface taken 2 K below the air for night-sky cooling — so pick your nearest weather station for your own build-up: the result can change from one station to another.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of brick-slip external wall insulation?
External wall insulation finished with brick slips on a solid 9-inch brick wall needs about 110mm of grey EPS (Wetherby Epsitherm 70E, λ 0.032) to meet the 0.30 W/m²K Approved Document L asks of an upgraded wall: U-Monkey gives 0.28 with the system’s certified fixings counted (7 per m² at χ 0.004 W/K), and 100mm misses, at 0.31. The BBA certificate’s table puts 100mm at 0.30. Like U-Monkey, it takes the brick behind as protected (λ 0.56), as BR 443 does once a wall has external insulation, and its figures are close to a calculation with no air-gap correction: U-Monkey gives 0.299 on that basis, and adds BR 443’s default correction otherwise. The slips themselves add almost nothing: what sets them apart from render is the finish, the weight and the fixings.
How thick does brick-slip external insulation need to be to meet Building Regulations?
About 110mm of grey EPS (λ 0.032) on a 9-inch solid brick wall, counting the system’s fixings: U-Monkey gives 0.28 W/m²K against the 0.30 Approved Document L sets for an upgraded wall (Table 4.3). The system’s BBA certificate puts 100mm at 0.30; U-Monkey reads 0.31 there (0.306), because it adds BR 443’s default air-gap correction, which the certificate’s figures appear to leave out: without it, 0.299. Both take the brick behind as protected (λ 0.56). With higher-grade EPS (λ 0.030) 100mm reaches 0.29; with mineral wool (λ 0.036) it takes about 120mm.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.