A warehouse floor of 100 × 50m — a 200mm ground-bearing concrete slab with no insulation under it — has a U-value of about 0.19 W/m²K on sand or gravel and 0.15 on clay, because a big floor loses heat mostly round its edge: its perimeter-to-area ratio is only 0.06. That is just over the 0.18 Approved Document L Volume 2 sets for a floor on sand or gravel, and a 1m strip of 50mm PIR round the edge under the slab takes it to 0.16 (on clay, 0.13), with no insulation under the rest. BR 443 says it plainly: “Very large floors can have low U-values without all-over insulation.” A smaller shed needs more: 60 × 40m, uninsulated, reads 0.24.
Every layer editable · live U-value · Part L Volume 2 targets (buildings other than dwellings) · free PDF report
The build-up (outside → inside)
- 200mm power-floated reinforced concrete slab (not counted in R_f: BR 443 leaves out dense slabs)
- Polythene DPM
- No insulation under the slab except a 1m wide strip of 50mm PIR (λ 0.022) round the perimeter — horizontal edge insulation, BS EN ISO 13370 Annex D
- Ground: sand or gravel (λ 2.0). Floor 100 × 50m: exposed perimeter 300m, area 5,000m², walls 300mm thick
The pre-filled link opens in the England · non-domestic regime with the floor’s geometry set — exposed perimeter 300m, area 5,000m², wall thickness 300mm, sand or gravel (λ 2.0) — and edge insulation horizontal, 1.0m wide, 50mm at λ 0.022. The concrete slab is not counted in R_f, as BR 443 directs for dense slabs, and finishes are ignored. The U-value is for the floor as a whole; the junctions round it are separate.
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| 100 × 50m (P/A 0.06), no insulation, sand or gravel | ≈ 0.19 | Misses 0.18 (0.189) |
| Same, on clay (λ 1.5) | ≈ 0.15 | Meets 0.18 with no insulation (0.146) |
| Same, sand or gravel, 1m strip of 50mm PIR at the edge | ≈ 0.16 | As pre-filled (0.163) |
| Same, on clay, with the 1m edge strip | ≈ 0.13 | 0.125 |
| Same, sand or gravel, 50mm PIR 1m down the foundation (vertical) | ≈ 0.15 | 0.151: vertical edge insulation does a little more |
| 25mm PIR under the whole slab, sand or gravel | ≈ 0.13 | 0.133 |
| 50mm PIR under the whole slab | ≈ 0.11 | 0.111 |
| 60 × 40m (P/A 0.083), no insulation, sand or gravel | ≈ 0.24 | Fails 0.18 |
| 60 × 40m with the 1m edge strip | ≈ 0.21 | Still fails: a floor this size needs insulation under the slab |
| 60 × 40m, 25mm PIR all over | ≈ 0.17 | 0.167 |
| 120 × 60m (P/A 0.05), no insulation, sand or gravel | ≈ 0.16 | Meets 0.18 with no insulation (0.163) |
| 150 × 80m (P/A 0.038), no insulation | ≈ 0.13 | 0.132 |
| 200 × 100m (P/A 0.03), no insulation | ≈ 0.11 | 0.108 |
Figures computed to BS EN ISO 13370 with BR 443 conventions, exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up and the footprint and depth shown: your products, thicknesses, perimeter, area and ground will move the number, and that's what the calculator is for.
What changes the number
A floor on the ground is calculated by BS EN ISO 13370, not layer by layer, because most of its heat goes down into the ground and back out at the edge: the bigger the floor, the further its middle is from the edge and the less it loses. The standard works from the characteristic dimension B′ = A/(½P) — 33m for this 100 × 50m floor, about 3m for a small house — and BR 443 (2019) §9 sums it up: “Very large floors can have low U-values without all-over insulation”, and the floor U-value “decreases as the ratio of perimeter to area decreases”. The perimeter is every exposed wall, including walls to unheated spaces; walls to heated neighbours are left out. The ground matters as much as the size: BR 443 gives clay or silt λ 1.5, sand or gravel 2.0 and rock 3.5 W/m·K and says “the ground type in the UK is most commonly clay”, which takes this floor from 0.19 to 0.15. U-Monkey starts on sand or gravel, the cautious choice, so set yours from the site investigation. Edge insulation is a correction to the floor’s U-value (BS EN ISO 13370 Annex D), horizontal under the slab edge or vertical down the foundation, and only the more effective of the two counts; BR 443’s 2006 edition adds that edge insulation “will usually be needed to avoid thermal bridging at the perimeter” — the floor-to-wall junction’s own loss is a Ψ-value, not part of the floor U-value. Approved Document L Volume 2 sets 0.18 for a floor in its 2021 and 2026 editions. For a new building the test is the whole-building calculation (the BER and BPER against the TER and TPER): the NCM notional building gives a side-lit building’s floor 0.15 and a top-lit one’s 0.22, but where the floor’s own uninsulated value is below 0.15 “this lower value must be used in the Notional building” (NCM Modelling Guide 2021, paragraph 36) — so where a big shed’s uninsulated floor is already under 0.15, the notional floor is no better and the floor’s U-value costs nothing against the target — though the uninsulated slab edge’s thermal bridge still counts in the actual building. BR 443 adds that, as a floor’s U-value falls with its perimeter-to-area ratio, “the U-value can be obtained for the smallest intended building”: worth doing where a shed may be split into smaller units. Insulation under a racked warehouse slab has to carry the racking: specify its compressive strength for the loads.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a building's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a warehouse floor slab?
A warehouse floor of 100 × 50m — a 200mm ground-bearing concrete slab with no insulation under it — has a U-value of about 0.19 W/m²K on sand or gravel and 0.15 on clay, because a big floor loses heat mostly round its edge: its perimeter-to-area ratio is only 0.06. That is just over the 0.18 Approved Document L Volume 2 sets for a floor on sand or gravel, and a 1m strip of 50mm PIR round the edge under the slab takes it to 0.16 (on clay, 0.13), with no insulation under the rest. BR 443 says it plainly: “Very large floors can have low U-values without all-over insulation.” A smaller shed needs more: 60 × 40m, uninsulated, reads 0.24.
Does a warehouse floor need insulation?
Often only at the edge, sometimes not at all. On sand or gravel an uninsulated slab meets Approved Document L’s 0.18 once the floor is about 120 × 60m (0.16), and a 100 × 50m floor gets there with a 1m strip of 50mm PIR round the edge (0.16); on clay, a 100 × 50m slab is 0.15 with nothing. A 60 × 40m unit needs insulation under the slab: 25mm of PIR all over gives 0.17. Calculate your own floor in U-Monkey with its real perimeter, area and ground — and the slab edge still needs detailing against thermal bridging.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (Approved Document L Volume 2 for buildings other than dwellings, and the Welsh and Scottish equivalents), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Different build-up? See the full floor U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? For a building other than a dwelling, U-values feed the SBEM calculation that checks the building’s emission and primary energy rates against their targets (BER and BPER against TER and TPER) — and the non-domestic U-value page has the Volume 2 limits. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.