A single-skin (102.5mm) brick garage wall lined with a stud wall — kept 25mm off the brick, 100mm PIR between the studs and plasterboard — comes out at about 0.28 W/m²K, inside the 0.30 Approved Document L asks of a retained wall insulated internally (Table 4.3; paragraph 4.12(b) names garage conversions). The bare brick is about 3.3. 75mm of PIR gives about 0.34 and misses, and so, by a whisker, does 89mm (0.301); 100mm PIR plus 25mm across the studs reaches about 0.20. A wall built in the old door opening is a new wall and needs 0.18.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- 102.5mm single-skin brick (or 100mm block)
- 25mm clear gap, keeping the timber off the brick
- 100mm PIR between 100mm timber studs (15% timber)
- Plasterboard
The pre-filled link opens as a retained wall being upgraded, judged against Approved Document L’s 0.30 for internal insulation (2021 edition, Table 4.3). Studs at 15% timber (BR 443).
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| Bare 102.5mm brick | ≈ 3.30 | The starting point |
| 75mm PIR between studs | ≈ 0.34 | Misses 0.30 |
| 89mm PIR between CLS studs | ≈ 0.30 | Misses: 0.301 before rounding |
| 100mm PIR between studs | ≈ 0.28 | As pre-filled: meets 0.30 |
| 100mm mineral wool between studs | ≈ 0.40 | Misses, and needs a vapour control layer |
| 100mm PIR between studs + 25mm PIR across them | ≈ 0.20 | |
| 100mm dense block instead of brick, same lining | ≈ 0.28 | The lining does the work |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
The lining does all the work; the brick is there to keep the weather out, and single-skin brick does not always manage that, which is why the studs usually stand clear of it on a gap. The 25mm gap counts as a low-emissivity air space because it faces the PIR’s foil, and the studs bridge 15% of the insulation, so a continuous layer across them gains more than deeper studs. With mineral wool between the studs and no vapour control, U-Monkey’s condensation check finds moisture building up year on year on the inside face of the brick. As pre-filled, with PIR, its ISO 13788 screening finds none, and it reports that as a screening result only, as PAS 2035 notes that an ISO 13788 check might not be sufficient for internal insulation on solid masonry.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a garage conversion wall (insulating single-skin brick)?
A single-skin (102.5mm) brick garage wall lined with a stud wall — kept 25mm off the brick, 100mm PIR between the studs and plasterboard — comes out at about 0.28 W/m²K, inside the 0.30 Approved Document L asks of a retained wall insulated internally (Table 4.3; paragraph 4.12(b) names garage conversions). The bare brick is about 3.3. 75mm of PIR gives about 0.34 and misses, and so, by a whisker, does 89mm (0.301); 100mm PIR plus 25mm across the studs reaches about 0.20. A wall built in the old door opening is a new wall and needs 0.18.
What U-values do I need for a garage conversion?
In England, Approved Document L treats the garage’s existing walls, floor and roof as retained elements (paragraph 4.12(b)): anything worse than the Table 4.3 threshold should be upgraded to its “improved” value — 0.30 for a wall insulated internally (0.55 where a cavity can be filled), 0.25 for the floor and 0.16 for the roof — so far as that is technically and functionally feasible with a simple payback of 15 years or less. New elements meet Table 4.2: 0.18 for the wall in the old door opening and 1.4 for new windows and doors. Building Control will ask for the calculations.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.