A ground floor with wet underfloor heating — pipes in a 65mm screed on 100mm of PIR over the slab — has a U-value of about 0.17 W/m²K for a typical 30m perimeter / 50m² floor, inside the 0.18 limiting value for a new floor; 125mm gives about 0.15, and 150mm about 0.13, the new-build notional figure. BS EN 1264-4 also sets a minimum for the insulation under the pipes, a thermal resistance of 1.25 m²K/W over the ground (about 28mm of PIR), so for a UK ground floor it is the U-value that sets the thickness.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- (Ground resistance via BS EN ISO 13370 — P/A dependent)
- Concrete slab (not counted — BR 443)
- 100mm PIR
- 65mm sand/cement screed with the heating pipes
BS EN 1264-4 Table 1 (as manufacturers reproduce it): 0.75 m²K/W over a heated room; 1.25 over an unheated or intermittently heated room, the ground, or outside air down to 0°C; 1.50 down to −5°C; 2.00 down to −15°C. The pre-filled link opens at U-Monkey’s default 30m / 50m² (P/A 0.6).
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| 50mm PIR | ≈ 0.29 | Meets BS EN 1264-4, not Part L |
| 75mm PIR | ≈ 0.22 | |
| 100mm PIR | ≈ 0.17 | As pre-filled: meets 0.18 |
| 125mm PIR | ≈ 0.15 | |
| 150mm PIR | ≈ 0.13 | Meets the 0.13 notional (0.125) |
| 150mm EPS (λ 0.038) | ≈ 0.20 | |
| 100mm PIR, small extension floor (P/A 0.9) | ≈ 0.18 | Misses 0.18: 0.183 |
Figures computed to BS EN ISO 13370 with BR 443 conventions, exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up and the footprint and depth shown: your products, thicknesses, perimeter, area and ground will move the number, and that's what the calculator is for.
What changes the number
The insulation under the screed does it all; the screed and the floor finish barely register in the U-value but matter to the heating, because everything above the pipes slows the heat into the room. Run an edge strip of insulation round the screed so it does not lose heat sideways into the walls, and remember that a heated floor runs warmer than the room, so it loses a little more than its U-value at room temperature suggests. On a small extension the perimeter-to-area ratio can tip 100mm over the limit, though Approved Document L lets an extension’s floor be calculated with the perimeter and area of the whole enlarged home (Table 4.2, note 5); enter your own floor.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
Underfloor heating on a ground floor: insulation and U-value?
A ground floor with wet underfloor heating — pipes in a 65mm screed on 100mm of PIR over the slab — has a U-value of about 0.17 W/m²K for a typical 30m perimeter / 50m² floor, inside the 0.18 limiting value for a new floor; 125mm gives about 0.15, and 150mm about 0.13, the new-build notional figure. BS EN 1264-4 also sets a minimum for the insulation under the pipes, a thermal resistance of 1.25 m²K/W over the ground (about 28mm of PIR), so for a UK ground floor it is the U-value that sets the thickness.
How much insulation do I need under underfloor heating?
Two rules apply and the stricter wins. BS EN 1264-4 asks for a thermal resistance under the pipes of at least 0.75 m²K/W over a heated room, 1.25 over an unheated room or the ground, and up to 2.00 over outside air in a cold climate; 1.25 is about 28mm of PIR. A ground floor in a new home or extension also needs a U-value of 0.18 W/m²K or better under Approved Document L, which for a typical floor takes about 100mm of PIR. So on the ground, the U-value decides.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Different build-up? See the full floor U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.