Open-cell spray foam (λ 0.039) sprayed 150mm deep between the rafters, under a breathable underlay, with the air and vapour control layer its BBA certificate requires and a plasterboard ceiling under it, gives a pitched roof a U-value of about 0.31 W/m²K — well short of the 0.16 Approved Document L asks of a renovated roof. 200mm, the most its BBA certificate allows, gives about 0.24, and 150mm with 30mm more between battens under the rafters about 0.25, the figure the certificate gives for that build-up. Closed-cell foam is better per millimetre (λ about 0.025–0.028) but far less vapour-open. And before choosing either, know that surveyors and mortgage lenders treat spray foam with caution: the RICS says its presence could affect a surveyor’s opinion of value.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- Tiles on battens (outside a ventilated layer: not counted)
- Breathable (LR) roofing underlay
- 150mm open-cell spray foam between 150mm rafters (12% timber)
- Air and vapour control layer (AVCL), as the certificate requires
- 12.5mm plasterboard
Open-cell foam as Huntsman’s H2Foam Lite (λ 0.039, and μ 4.4 for the condensation check, BBA 23/7062), closed-cell as U-Monkey’s generic entry (λ 0.026, μ 60). Rafters at 12%, battens under them at 11.8%; the tiles and their batten space lie outside a ventilated layer and are not counted. The pre-filled link opens as an upgraded existing roof, judged against Approved Document L’s 0.16 (2021 edition, Table 4.3).
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| 100mm open-cell between the rafters | ≈ 0.44 | |
| 150mm open-cell between the rafters | ≈ 0.31 | As pre-filled |
| 175mm open-cell (deeper rafters) | ≈ 0.27 | |
| 200mm open-cell (deeper rafters) | ≈ 0.24 | The most BBA 23/7062 allows |
| 150mm open-cell + 30mm between battens under the rafters | ≈ 0.25 | BBA 23/7062 Table 6: 0.25 |
| 100mm closed-cell (λ 0.026) | ≈ 0.35 | |
| 125mm closed-cell | ≈ 0.29 | |
| 150mm open-cell + 50mm PIR under the rafters | ≈ 0.18 | The foil-faced board, taped, is the AVCL |
| For comparison: 150mm PIR between the rafters + 50mm under | ≈ 0.14 |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
Spray foam’s appeal is that it fills round the rafters and seals the roof in one pass, but it is not a high performer: open-cell foam is about as conductive as mineral wool (λ 0.039), and with the rafters bridging 12% of it, 150mm only reaches 0.31. A continuous layer under the rafters helps most, as in any rafter roof: 50mm of PIR takes 150mm of foam to about 0.18. The BBA certificate for Huntsman’s H2Foam Lite E (23/7062) limits it to roofs with a breathable underlay, requires an air and vapour control layer under it on the warm side, asks for a pre-installation survey that includes a condensation risk assessment and timber below 20% moisture content, and caps it at 200mm. Closed-cell foams such as BASF’s Walltite (NSAI 13/0377, λ 0.025–0.028) and Huntsman’s Heatlok HFO Pro (Kiwa, 0.025) insulate better but resist vapour far more, and the RICS warns that foam can seal in moisture unless adequate precautions are taken. Both kinds hide the timbers: the RICS consumer guide (2023) notes that a roof structure covered in foam “cannot be fully seen or inspected”, the Property Care Association’s inspection protocol (2023) treats foam sprayed onto the tiles or onto a high-resistance felt as higher risk, and LABC Warranty decided in 2022 not to accept spray foam in roofs.
Condensation risk with spray foam
Open-cell foam is vapour-open, so the layer under it decides the condensation risk. The BBA certificate requires an air and vapour control layer on the warm side, and with one, as pre-filled, U-Monkey’s free BS EN ISO 13788 check finds only a trace of seasonal condensation at the underlay (about 1 g/m² in December) and gives a conditional pass, depending on the underlay staying low-resistance (sd 0.05m or less).
Leave the AVCL out — as many installations have — and the check predicts about 1.2 kg/m² of condensation on the underside of the underlay by February, evaporating in summer, and rates the roof “not a pass”: BS 5250:2021 asks a warm pitched roof for an AVCL on the warm side, and the calculation can’t see the room air leaking into the roof, which is how most moisture gets there. Closed-cell foam resists vapour far more (U-Monkey takes μ 60, against 4.4 for this open-cell foam), and without an AVCL the check predicts only about 55 g/m² with 100mm of it, but still rates the roof “not a pass”. Foil-faced PIR under the rafters, taped at its joints, can do the AVCL’s job: with 50mm of it under 150mm of foam the check finds no condensation in any month.
Opens pre-filled. The condensation verdict sits just under the U-value — tap it for the full month-by-month check, the surface-mould (fRsi) check included. If it isn’t a pass, How to fix it tests the usual remedies on your build-up — a vapour control layer, a vapour-open underlay, a ventilated void, a warm deck — and applies the one you pick in a tap, with Undo.
Need it in writing for Building Control? The full condensation risk analysis report is £25 +VAT (£30 inc VAT), or included on Monkey Pro Unlimited — see an example report (PDF), or read what building control expects the analysis to show.
It is a screening to BS EN ISO 13788 (the Glaser method), honestly labelled as one: it does not model air leakage, rain or moisture stored in materials, so for high-risk or heritage constructions a full hygrothermal simulation (BS EN 15026) is the right next step. Figures above use the app’s defaults — Manchester (Ringway) climate, humidity class 3 (dwellings with high or unknown occupancy), a 1-in-10 design year and, on a roof, the surface taken 2 K below the air for night-sky cooling — so pick your nearest weather station for your own build-up: the result can change from one station to another.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of spray foam insulation in a pitched roof?
Open-cell spray foam (λ 0.039) sprayed 150mm deep between the rafters, under a breathable underlay, with the air and vapour control layer its BBA certificate requires and a plasterboard ceiling under it, gives a pitched roof a U-value of about 0.31 W/m²K — well short of the 0.16 Approved Document L asks of a renovated roof. 200mm, the most its BBA certificate allows, gives about 0.24, and 150mm with 30mm more between battens under the rafters about 0.25, the figure the certificate gives for that build-up. Closed-cell foam is better per millimetre (λ about 0.025–0.028) but far less vapour-open. And before choosing either, know that surveyors and mortgage lenders treat spray foam with caution: the RICS says its presence could affect a surveyor’s opinion of value.
Will spray foam insulation stop me selling or remortgaging?
It can make it harder. The RICS’s consumer guide (2023) says spray foam is a factor that could affect a surveyor’s opinion of value and that a surveyor may ask for an independent specialist report; lenders that do accept it usually want one, made to the Property Care Association’s inspection protocol, and some won’t lend at all. Have the specialist report, the product’s BBA or Kiwa certificate and the installer’s paperwork ready. Removing the foam is possible but disruptive, and the timbers then need inspecting — the very thing the foam had prevented.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full roof U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.