An extension wall built with the house’s usual 100mm cavity — brick, 100mm of λ 0.032 cavity batts, 100mm aircrete blocks and plasterboard on dabs — comes out at about 0.25 W/m²K, well short of the 0.18 Approved Document L sets for a new wall in an existing home. Lining it with 52.5mm PIR insulated plasterboard (40mm of PIR) brings it to about 0.17, which meets; a 37.5mm board gives 0.19 and misses. The alternative is a wider cavity: 150mm of the same batts meets 0.18 with thermal-grade aircrete (0.176) but not quite with standard aircrete (0.181).
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- 102.5mm brick outer leaf
- 100mm cavity, fully filled with λ 0.032 glass mineral wool batts
- 100mm aircrete block inner leaf (mortar joints counted)
- 15mm gap on plaster dabs (20% dabs, BR 443 §4.6.1)
- 40mm PIR insulated plasterboard core
- 12.5mm plasterboard facing
The pre-filled link opens as a new element in an existing home, judged against Approved Document L’s 0.18 (2021 edition, Table 4.2). Batts at λ 0.032 (Knauf DriTherm Cavity Slab 32 in U-Monkey’s library).
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| 100mm cavity, λ 0.032 batts, plasterboard on dabs | ≈ 0.25 | Misses 0.18 |
| + 25mm PIR insulated plasterboard (37.5mm board) | ≈ 0.19 | Misses: 0.1949 |
| + 40mm PIR insulated plasterboard (52.5mm board) | ≈ 0.17 | As pre-filled: meets 0.18 |
| 100mm cavity, dense block inner leaf, + 40mm PIR lining | ≈ 0.19 | Dense blocks undo it: 0.189 |
| 150mm cavity, λ 0.032 batts, standard aircrete | ≈ 0.18 | Misses by a whisker: 0.181 |
| 150mm cavity, λ 0.032 batts, thermal aircrete (λ 0.11) | ≈ 0.18 | Meets: 0.176 |
| 150mm cavity, 100mm PIR + 50mm clear | ≈ 0.17 |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
Matching the house usually means keeping its brick line and a 100mm cavity, and full fill can’t reach 0.18 there on its own: the lining has to do the rest, at the cost of about 40mm more room than plain plasterboard on each outside wall. Widening the cavity to 150mm puts the extra insulation where it costs no floor space, at the price of a wider wall and foundation, and the result then hangs on the inner leaf: standard aircrete 0.181, thermal-grade 0.176, dense block about 0.20. Mortar joints in the blockwork, the dabs behind the plasterboard and the wall ties all nibble at it; U-Monkey counts the mortar and the dabs for you, as BR 443 requires, and offers to add the ties.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of an extension cavity wall (what reaches 0.18)?
An extension wall built with the house’s usual 100mm cavity — brick, 100mm of λ 0.032 cavity batts, 100mm aircrete blocks and plasterboard on dabs — comes out at about 0.25 W/m²K, well short of the 0.18 Approved Document L sets for a new wall in an existing home. Lining it with 52.5mm PIR insulated plasterboard (40mm of PIR) brings it to about 0.17, which meets; a 37.5mm board gives 0.19 and misses. The alternative is a wider cavity: 150mm of the same batts meets 0.18 with thermal-grade aircrete (0.176) but not quite with standard aircrete (0.181).
What U-value does an extension wall need?
In England, 0.18 W/m²K: an extension’s walls are new elements in an existing dwelling, so Approved Document L’s Table 4.2 applies (2021 edition; the 2026 edition, which takes effect on 24 March 2027, keeps 0.18 in its Table 3.2). The same table asks 0.15 of the roof, 0.18 of the floor and 1.4 of new windows and doors. A lesser standard may be appropriate for a wall where meeting it would reduce the floor area of the room by more than 5% (Table 4.2, note 3).
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.