Expanded cork board (Amorim ICB, λ 0.040) 60mm thick, bonded inside a solid 9-inch brick wall and finished in lime plaster, gives a U-value of about 0.50 W/m²K, from about 2.1 — about the same as 60mm of wood fibre, and the 0.49 the ASBP’s specification generator gives for 60mm of cork. 40mm (0.67) is the thinnest standard board that meets the 0.7 Approved Document L sets as a minimum for an upgraded wall, and its 0.30 takes about 120mm, inside (0.29) or outside (0.29). Cork earns its place on what differs from wood fibre: it does not take up water by capillary action, and it is more vapour-resistant (μ 20, against 3–5).
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- 215mm solid brick
- 15mm lime plaster (existing, or a hydraulic lime levelling coat)
- 10mm lime-cork adhesive (modelled as lime plaster)
- 60mm Amorim expanded cork board (ICB, λ 0.040, μ 20)
- 10mm meshed lime base coat
- 3mm lime top coat
Amorim expanded corkboard (ICB) at λ 0.040 and μ 20 (Amorim technical features; ACERMI 0.040, EU declared 0.039). The adhesive (Secil Isovit, an NHL and cork mix) publishes no λ and is entered as lime plaster, like the base and top coats. External rows: 3mm lime top coat and 10mm base coat outside the cork, 10mm adhesive, 215mm brick (protected by the cork outside it: λ 0.56, BR 443 §7, mortar joints counted, §4.2), 13mm plaster inside, with the fixings left out (Tŷ-Mawr names no fixing type). The pre-filled link opens as an upgraded solid wall.
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| Internal: 40mm cork | ≈ 0.67 | Meets the 0.7 backstop |
| Internal: 50mm | ≈ 0.58 | |
| Internal: 60mm | ≈ 0.50 | As pre-filled; ASBP: 0.49 |
| Internal: 80mm | ≈ 0.41 | |
| Internal: 100mm | ≈ 0.34 | |
| Internal: 120mm | ≈ 0.29 | Meets the 0.30 (0.293) |
| Internal: 60mm at the declared λ 0.039 | ≈ 0.50 | 0.495 |
| External: 100mm cork, lime base coat | ≈ 0.33 | |
| External: 120mm | ≈ 0.29 | Tŷ-Mawr’s external design for 0.30 or better |
| External: 140mm | ≈ 0.25 | |
| External: 160mm | ≈ 0.23 | |
| 500mm sandstone or granite + 60mm cork inside | ≈ 0.52 | Fails the condensation check (about 650 g/m² left at the year end) |
| 500mm limestone + 60mm cork inside | ≈ 0.49 | Fails the condensation check (about 400 g/m² left) |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
Thickness does the work, as with any board, and cork’s λ (Amorim declares 0.039 for its EU label and 0.040 under ACERMI; 0.040 is used here) puts it level with wood fibre: 60mm takes a plastered 9-inch brick wall from about 2.1 to 0.50, 120mm to 0.29. What sets cork apart is the moisture behaviour. Amorim’s expanded corkboard “does not absorb water by capillary action” and has a vapour resistance factor of 20 — about 1.2m of equivalent air at 60mm, four to seven times less open than 60mm of wood fibre — so it neither wicks moisture away like a capillary-active board nor lets vapour through as freely. That is part of why it is also used outside: Tŷ-Mawr’s external design puts 120mm of cork on a lime levelling coat, with insulated fixings at about 8 per m² and a meshed lime-cork base coat, for 0.30 or better — U-Monkey gives 0.29 with the fixings left out (add them in the fixings sheet to suit the fixing chosen). The board is Euroclass E (Amorim’s external system is B), so in England it can’t form part of the external wall of a relevant building — one with a storey at least 18m above ground that contains dwellings, an institution or rooms for residential purposes — inside or out (regulation 7(2)). Approved Document L asks an upgraded solid wall for 0.30 (Table 4.3), allows a lesser standard where internal insulation would take more than 5% of the room’s floor area (note 6), and generally no worse than 0.7 (paragraph 4.13); outside, note 6 doesn’t apply. Inside or out, cure damp and keep driving rain out first — Tŷ-Mawr calls external protection from driving rain essential for internal insulation — and use lime adhesives and vapour-permeable paints.
Condensation risk with cork internal insulation
For the pre-filled wall, U-Monkey’s free BS EN ISO 13788 check finds seasonal condensation at the back of the cork, where it meets the lime adhesive — a peak of 463 g/m² in March — that dries out fully over the summer, and rates the wall “screening only”: internal insulation on solid masonry needs a BS EN 15026 hygrothermal assessment before the result can be relied on, because a monthly calculation can’t see driving rain or liquid moisture moving through the brick. It also flags that the condensation forms against a bio-based insulant, which a prolonged wetting can damage. On 500mm of stone the same 60mm fails instead: condensate builds up year on year (about 650 g/m² left at the end of the year on sandstone or granite, 400 on limestone).
The same cork outside the wall — 120mm on the brick, under a lime render — gets a straight pass: no condensation in any month. That is the general pattern for solid walls, and the reason internal insulation is the one that needs the extra care: keep the rain out, the joints and edges sealed, and the finishes vapour-permeable.
Opens pre-filled. The condensation verdict sits just under the U-value — tap it for the full month-by-month check, the surface-mould (fRsi) check included. If it isn’t a pass, How to fix it tests the usual remedies on your build-up — a vapour control layer on the warm side, a more vapour-open layer on the cold side, more insulation to warm the inside surface — and applies the one you pick in a tap, with Undo.
Need it in writing for Building Control? The full condensation risk analysis report is £25 +VAT (£30 inc VAT), or included on Monkey Pro Unlimited — see an example report (PDF), or read what building control expects the analysis to show.
It is a screening to BS EN ISO 13788 (the Glaser method), honestly labelled as one: it does not model air leakage, rain or moisture stored in materials, so for high-risk or heritage constructions a full hygrothermal simulation (BS EN 15026) is the right next step. Figures above use the app’s defaults — Manchester (Ringway) climate, humidity class 3 (dwellings with high or unknown occupancy), a 1-in-10 design year and, on a roof, the surface taken 2 K below the air for night-sky cooling — so pick your nearest weather station for your own build-up: the result can change from one station to another.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of cork insulation on a solid wall?
Expanded cork board (Amorim ICB, λ 0.040) 60mm thick, bonded inside a solid 9-inch brick wall and finished in lime plaster, gives a U-value of about 0.50 W/m²K, from about 2.1 — about the same as 60mm of wood fibre, and the 0.49 the ASBP’s specification generator gives for 60mm of cork. 40mm (0.67) is the thinnest standard board that meets the 0.7 Approved Document L sets as a minimum for an upgraded wall, and its 0.30 takes about 120mm, inside (0.29) or outside (0.29). Cork earns its place on what differs from wood fibre: it does not take up water by capillary action, and it is more vapour-resistant (μ 20, against 3–5).
Is cork better than wood fibre for insulating a solid wall?
Thermally they are level: λ 0.039–0.040 for cork, 0.038–0.040 for wood-fibre boards, so 60mm of either takes a 9-inch brick wall to about 0.49–0.50 W/m²K. The differences are in moisture and use. Wood fibre is capillary-active and very vapour-open (μ 3–5); cork does not take up water by capillary action and is more vapour-resistant (μ 20). In U-Monkey’s screening check, 60mm of cork inside a 9-inch brick wall leaves seasonal condensation that dries out each summer (on 500mm of stone it builds up instead), and 120mm of cork outside the wall none at all. Both are used outside as well as in, on lime-based systems.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.