The wall between a house and a thermally separated conservatory keeps the U-value it had as an outside wall: SAP 10.2 calculates the dwelling “as if it were not present” (§3.3.3), so a filled 50mm cavity wall stays at about 0.60 W/m²K and a solid 9-inch brick wall at about 2.1. BR 443 does allow an unheated space such as a conservatory to be counted as an extra resistance, Ru — about 0.05–0.07 m²K/W for an older, leaky conservatory and 0.15 for a well-glazed, airtighter one, by SAP’s own formula (4) — which would take the cavity wall to 0.58 or 0.55: a small effect, and not one SAP uses. Take the doors out or extend the heating into the conservatory, and that wall stops being the boundary at all.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- (The conservatory beyond: disregarded, as SAP 10.2 §3.3.3 does for a thermally separated one)
- 102.5mm brick outer leaf
- 50mm cavity filled with blown mineral wool
- 100mm dense concrete block inner leaf
- 13mm plaster
Calculated as an external wall, as SAP 10.2 §3.3.3 does for a thermally separated conservatory; the Ru rows add BR 443 §5’s unheated-space resistance, U = 1/(1/Uo + Ru), for the example conservatory in “What changes the number” (SAP 10.2 formula (4), the floor left out as it says). The pre-filled link opens the wall facing outside air; U-Monkey takes an Ru under “On the other side” → “Another unheated space”.
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| Filled 50mm cavity, the conservatory disregarded (SAP 10.2) | ≈ 0.60 | As pre-filled: how SAP and RdSAP count it |
| Same, counting an older double-glazed conservatory (Ru 0.07) | ≈ 0.58 | Ru from SAP formula (4) for the example below |
| Same, with a well-glazed, airtighter conservatory (Ru 0.15) | ≈ 0.55 | |
| Unfilled 50mm cavity | ≈ 1.67 | |
| Unfilled 50mm cavity, Ru 0.15 | ≈ 1.34 | |
| Solid 215mm brick, plastered | ≈ 2.10 | |
| Solid 215mm brick, Ru 0.15 | ≈ 1.60 | Where an Ru makes most difference |
| A new separating wall: 100mm PIR partial fill, aircrete, plasterboard on dabs | ≈ 0.17 | Meets the 0.18 for a new wall in an existing dwelling (Table 4.2) |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for. Rows that give an Ru include the unheated space beyond the element as an extra resistance, U = 1/(1/Uo + Ru) (SAP 10.2 §3.3 formula (3); BR 443 §5), which the calculator applies under “On the other side”.
What changes the number
Two rules meet here. SAP 10.2 §3.3.3 says a conservatory is thermally separated when it is divided from the house by walls, floors, windows and doors with U-values similar to (or, for a new conservatory, no worse than) the dwelling’s own exposed elements, and new doors and windows draught-stripped to match; then “the calculation should be undertaken as if it were not present” — the wall behind it counts as an outside wall, and the conservatory’s floor area is left out. BR 443 §5, the U-value conventions, lists conservatories among the unheated spaces whose effect can be added to a wall as a resistance Ru, from Ru = Ai / (ΣAe·Ue + 0.33·n·V). For an example conservatory 3.5 × 3.0m with 2.4m walls under a roof averaging 2.5m (an 8.4m² wall to the house, 22.8m² of glazed walls, a 10.5m² roof, 26m³ of air), older double glazing at 2.8 and a polycarbonate roof at 2.4 with SAP’s default three air changes an hour give Ru ≈ 0.07 (single glazing, at about 4.8, gives 0.05); modern double glazing at 1.4, a roof at 1.5 and one air change an hour give about 0.15. Either way the effect on a filled cavity wall is a few hundredths, and on a solid brick wall larger (2.10 → 1.60); SAP leaves it out regardless. Approved Document L exempts a new conservatory of up to 30m² at ground level from the energy requirements if the wall, door or window between it and the house is kept (or replaced with one), and the heating is not extended into it (paragraph 0.14; regulation 21); remove that separation or heat the conservatory, and regulation 21(4) brings it within them — see GlazeMonkey’s conservatory guide.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of the wall between a house and a conservatory?
The wall between a house and a thermally separated conservatory keeps the U-value it had as an outside wall: SAP 10.2 calculates the dwelling “as if it were not present” (§3.3.3), so a filled 50mm cavity wall stays at about 0.60 W/m²K and a solid 9-inch brick wall at about 2.1. BR 443 does allow an unheated space such as a conservatory to be counted as an extra resistance, Ru — about 0.05–0.07 m²K/W for an older, leaky conservatory and 0.15 for a well-glazed, airtighter one, by SAP’s own formula (4) — which would take the cavity wall to 0.58 or 0.55: a small effect, and not one SAP uses. Take the doors out or extend the heating into the conservatory, and that wall stops being the boundary at all.
Do I need to insulate the wall between my house and conservatory?
Not for SAP or an EPC: a thermally separated conservatory is disregarded, so the wall behind it keeps the U-value it had as an outside wall — about 0.60 W/m²K for a filled cavity wall, 2.1 for solid brick — and improving it helps exactly as much as improving any outside wall. The conservatory itself only buffers it a little (an Ru of about 0.05–0.15 m²K/W). The wall matters most when it is taken away: knock through, or extend the heating into the conservatory, and the conservatory’s own glazing, roof and dwarf walls become the outside of the house, with the Building Regulations’ energy requirements applying to them (regulation 21(4)).
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.