A concrete wall with rainscreen cladding — 200mm reinforced concrete lined inside with plasterboard on dabs, 200mm of ROCKWOOL RainScreen Duo Slab (λ 0.035) outside it and fibre-cement panels on a ventilated subframe — has a U-value of about 0.17 W/m²K for the insulation alone, and about 0.23 once the aluminium cladding brackets are counted at one per m² with the point thermal transmittance Hilti publishes for its standard bracket into concrete (χ 0.064 W/K). Stainless steel brackets (χ 0.011) give 0.18; with no calculated χ, BR 443 adds 0.30 and the wall reads 0.47, failing Approved Document L Volume 2’s 0.26 at any thickness. On a rainscreen the bracket choice moves the U-value more than the insulation does.
Every layer editable · live U-value · Part L Volume 2 targets (buildings other than dwellings) · free PDF report
The build-up (outside → inside)
- Fibre cement rainscreen panels (8mm) and their ventilated cavity: not counted, BR 443 §4.8.5
- 200mm ROCKWOOL RainScreen Duo Slab (λ 0.035), pierced by aluminium helping-hand brackets with plastic isolators, one per m² (χ 0.064 W/K each: Hilti’s calculated value for its MFT-MFI medium bracket into 180mm concrete)
- 200mm reinforced concrete wall (λ 2.3)
- Plasterboard on dabs (BR 443 §4.6.1: 20% plaster dabs)
Brackets as Hilti’s Technical Manual for ventilated façades (Section 6, U-value, 2019) gives them for its MFT-MFI medium aluminium bracket with a polypropylene isolator into 180mm concrete with λ 0.035 insulation: χ 0.0638 W/K at 100mm, 0.0642 at 160mm and 0.0634 at 200mm (interpolated in the source), entered as 0.064 at one bracket per m² — a round figure to show the scale; enter your own system’s χ and count. Stainless rows use its VTR stainless bracket (0.017 at 100mm, 0.0106 at 200mm), the thermally separated row its polyamide-separated brackets (about 0.001–0.0035). The cladding and its ventilated cavity are disregarded and Rse becomes 0.13 (BS EN ISO 6946 §6.9.4; BR 443 §4.8.5); the plaster dabs are bridged as BR 443 §4.6.1 directs. Opens in the England · non-domestic regime.
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| Insulation alone, no brackets counted (U0) | ≈ 0.17 | Where BR 443 does not let you stop: brackets through insulation must be counted |
| 150mm, aluminium brackets, 1 per m² | ≈ 0.28 | Fails 0.26 (0.280) |
| 200mm, aluminium, 1 per m² | ≈ 0.23 | As pre-filled (0.233) |
| 250mm, aluminium, 1 per m² | ≈ 0.20 | 0.203 |
| 200mm, aluminium, 1.5 per m² | ≈ 0.26 | Fails 0.26 (0.265) |
| 200mm, aluminium, 2 per m² | ≈ 0.30 | |
| 200mm, Hilti’s large aluminium bracket (χ 0.108), 1 per m² | ≈ 0.28 | Heavier cladding, bigger brackets |
| 200mm, stainless steel brackets (χ 0.011), 1 per m² | ≈ 0.18 | 0.179 |
| 200mm, stainless, 2 per m² | ≈ 0.19 | 0.190; ROCKWOOL’s own 3-D figure for 210mm on 200mm concrete with stainless brackets is 0.18 |
| 200mm, thermally separated brackets (χ 0.0035), 1 per m² | ≈ 0.17 | 0.172 |
| 200mm, brackets with no calculated χ: BR 443’s +0.30 | ≈ 0.47 | Fails 0.26 — no thickness passes with 0.30 added |
| 200mm NyRock Rainscreen 032 instead, aluminium, 1 per m² | ≈ 0.22 | 0.220 |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
BR 443 (2019) §4.8.5 treats a rainscreen in two parts. The cladding and its ventilated cavity drop out, and the outside surface resistance becomes 0.13; but “the effect of brackets or rails fixing the cladding to the wall behind must be taken into account” wherever they cross insulation — by a calculation of the whole wall, a linear thermal transmittance for rails, a point thermal transmittance χ for each bracket (U = U0 + Σχ·n), or, with no calculated result, “a conservative default value of 0.30 W/m²K”. Few bracket makers publish χ. Hilti’s technical manual for ventilated façades (2019, calculated to BS EN ISO 10211) is the fullest public set, and shows the range: about 0.064 W/K for its medium aluminium bracket with a polypropylene isolator into 180mm of concrete, 0.108 for the large one, 0.010–0.032 for stainless steel brackets and 0.001–0.0035 for brackets with a polyamide thermal separation; into 300mm of brick the same aluminium brackets lose roughly half as much. The count per m² comes from the subframe layout — rail spacing times bracket spacing, set by the cladding’s weight and the wind load — so heavy cladding costs twice. Insulation makers’ tables come from 3-D calculations with one named bracket system: ROCKWOOL gives 0.18 for 210mm of RainScreen Duo Slab on 200mm of concrete with stainless steel brackets, and 0.18 for 200mm of NyRock Rainscreen 032 on 150mm of concrete with Ash & Lacy’s AxiAL aluminium brackets, which come with isolation pads — use such figures for the system modelled, not yours. The concrete itself adds little resistance, but what the brackets fix into changes their χ, as the brick figures above show, so use the χ for your backing wall; slab edges, window reveals and parapets are junction Ψ-values on top. Approved Document L Volume 2 sets 0.26 for a wall (2021 and 2026), and the NCM notional building 0.18 for a side-lit building. Where the fire rules for a building restrict combustible materials in its external walls, check the insulation’s reaction-to-fire class against them.
Condensation risk with rainscreen on concrete
U-Monkey’s free BS EN ISO 13788 check finds no interstitial condensation in any month for the pre-filled wall: the concrete is on the warm side and the mineral wool outside it is vapour-open to the ventilated cavity, so any vapour that reaches it passes out.
The check is one-dimensional, through the insulation; the brackets are three-dimensional thermal bridges it cannot see. Keep the insulation tight round them, and treat the slab edges and openings as junctions.
Opens pre-filled. The condensation verdict sits just under the U-value — tap it for the full month-by-month check, the surface-mould (fRsi) check included. If it isn’t a pass, How to fix it tests the usual remedies on your build-up — a vapour control layer on the warm side, a more vapour-open layer on the cold side, more insulation to warm the inside surface — and applies the one you pick in a tap, with Undo.
Need it in writing for Building Control? The full condensation risk analysis report is £25 +VAT (£30 inc VAT), or included on Monkey Pro Unlimited — see an example report (PDF), or read what building control expects the analysis to show.
It is a screening to BS EN ISO 13788 (the Glaser method), honestly labelled as one: it does not model air leakage, rain or moisture stored in materials, so for high-risk or heritage constructions a full hygrothermal simulation (BS EN 15026) is the right next step. Figures above use the app’s defaults — Manchester (Ringway) climate, humidity class 3 (dwellings with high or unknown occupancy), a 1-in-10 design year and, on a roof, the surface taken 2 K below the air for night-sky cooling — so pick your nearest weather station for your own build-up: the result can change from one station to another.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a building's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of rainscreen cladding on a concrete or blockwork wall?
A concrete wall with rainscreen cladding — 200mm reinforced concrete lined inside with plasterboard on dabs, 200mm of ROCKWOOL RainScreen Duo Slab (λ 0.035) outside it and fibre-cement panels on a ventilated subframe — has a U-value of about 0.17 W/m²K for the insulation alone, and about 0.23 once the aluminium cladding brackets are counted at one per m² with the point thermal transmittance Hilti publishes for its standard bracket into concrete (χ 0.064 W/K). Stainless steel brackets (χ 0.011) give 0.18; with no calculated χ, BR 443 adds 0.30 and the wall reads 0.47, failing Approved Document L Volume 2’s 0.26 at any thickness. On a rainscreen the bracket choice moves the U-value more than the insulation does.
Aluminium or stainless steel rainscreen brackets?
For the U-value, stainless or thermally separated. On this wall one aluminium bracket per m² with an isolator (χ 0.064 W/K) adds 0.064 W/m²K, taking 200mm of insulation from 0.17 to 0.23, while a stainless bracket (χ 0.011) adds 0.011, giving 0.18; Hilti’s polyamide-separated brackets add about 0.0035. The χ is the bracket maker’s, for your backing wall and insulation depth. In U-Monkey, enter it with your number of brackets per m² in the insulation layer’s fixings sheet (“Certified χ per fixing or bracket”); with no χ, pick “Rainscreen brackets, no χ” for BR 443’s +0.30.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (Approved Document L Volume 2 for buildings other than dwellings, and the Welsh and Scottish equivalents), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a straw bale wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? For a building other than a dwelling, U-values feed the SBEM calculation that checks the building’s emission and primary energy rates against their targets (BER and BPER against TER and TPER) — and the non-domestic U-value page has the Volume 2 limits. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.