A straw bale wall of 450mm bales laid flat, with 25mm of lime plaster on each face, has a U-value of about 0.18 W/m²K (0.1797), just inside the 0.18 notional value, taking the λ of 0.080 that the German building approval for construction straw bales (2014, since lapsed) gave for heat flowing along the stalks. Which way the stalks run matters more than the size of the bale: set on edge, with the heat crossing the stalks (λ 0.052), a 350mm bale gives about 0.15 — better than the thicker bale laid flat. U-Monkey adds BR 443’s correction for air gaps in a single layer of insulation, about 0.009; most published figures leave it out.
Every layer editable · live U-value · Part L & Future Homes Standard targets · free PDF report
The build-up (outside → inside)
- 25mm lime render
- 450mm straw bales laid flat (stalks running through the wall: λ 0.080)
- 25mm lime plaster
λ 0.080 / 0.052 from the German building approval for construction straw bales (DIBt Z-23.11-1595, 2014, Table 2: design values along and across the stalks; it lapsed in 2019), which Passipedia repeats; U-Monkey’s library carries both bale orientations. The air-gap correction is BR 443’s level 1, which U-Monkey applies to a single layer of insulation.
Typical U-values for this construction
| Specification | U-value (W/m²K) | Notes |
|---|---|---|
| 450mm bales laid flat (λ 0.080, heat along the stalks) | ≈ 0.18 | As pre-filled: 0.1797 |
| 480mm bales laid flat | ≈ 0.17 | |
| 350mm bales on edge (λ 0.052, heat across the stalks) | ≈ 0.15 | Thinner, but better |
| 360mm bales on edge | ≈ 0.15 | 0.149 |
| 450mm at λ 0.065 (big bales, Passipedia) | ≈ 0.15 | |
| 450mm at λ 0.09 (a 2001 UK guide) | ≈ 0.20 | |
| 400mm EcoCocon straw panel (λ 0.0645) | ≈ 0.16 | EcoCocon quotes 0.150–0.152 without finishes or the air-gap correction |
| 400mm EcoCocon panel + 60mm wood-fibre render board | ≈ 0.13 | EcoCocon: 0.127–0.129 with 60mm of wood-fibre board |
Figures computed with the BS EN ISO 6946 combined method and BR 443 conventions — bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and the air-gap correction included — exactly as the pre-filled calculator works them out, with any pass or fail judged on the unrounded U-value. Indicative for the generic build-up shown: your products, thicknesses and (for floors) footprint will move the number, and that's what the calculator is for.
What changes the number
The bale’s orientation and density set the λ, and the published values differ. In a two-string bale the stalks run along the bale’s width, across the strings, so a bale laid flat carries heat along the stalks and one on edge across them: the German approval for construction straw (DIBt Z-23.11-1595, 2014, lapsed in 2019) gave design values of 0.080 and 0.052 for the two, and Passipedia quotes the same pair, with 0.065 for big bales; a newer European assessment for one maker’s bales (ETA-17/0247) declares 0.048 across the stalks, and Bath University’s tests for the ModCell panel proposed 0.064. A 2001 UK guide quotes 0.09 and, in the same breath, 0.13 for walls over 450mm thick — which would need λ of about 0.06; at 0.09 a 450mm wall is about 0.20. The plaster adds little to the U-value but makes the wall airtight, which straw needs. Prefabricated straw panels such as EcoCocon’s, straw packed into a timber frame, work the same way. U-Monkey applies BR 443’s air-gap correction for a single layer of insulation, about 0.009 on these walls; makers’ figures usually leave it out, which accounts for most of the gap between EcoCocon’s 0.150–0.152 for its 400mm panel without finishes and U-Monkey’s 0.164 with lime plaster both sides. With a second layer, the wood-fibre board, the correction drops away and the figures agree: 0.128 here with 60mm of STEICO Protect H, against EcoCocon’s 0.127–0.129 with 60mm of wood-fibre board.
Next: check the junctions
A U-value covers the flat area of an element — but heat also escapes where elements meet, and at modern U-values those junctions can be 20–30% of a dwelling's fabric heat loss. Now you know your U-values, model the junctions with the free ΨMonkey psi value calculator (no subscription; PDF reports £25 +VAT a junction):
Or read thermal bridging explained to see how junction Ψ-values feed your SAP calculation.
Frequently asked questions
What is the U-value of a straw bale wall?
A straw bale wall of 450mm bales laid flat, with 25mm of lime plaster on each face, has a U-value of about 0.18 W/m²K (0.1797), just inside the 0.18 notional value, taking the λ of 0.080 that the German building approval for construction straw bales (2014, since lapsed) gave for heat flowing along the stalks. Which way the stalks run matters more than the size of the bale: set on edge, with the heat crossing the stalks (λ 0.052), a 350mm bale gives about 0.15 — better than the thicker bale laid flat. U-Monkey adds BR 443’s correction for air gaps in a single layer of insulation, about 0.009; most published figures leave it out.
Is there a condensation risk in a straw bale wall?
A small, seasonal one if it is plastered with lime. U-Monkey’s free condensation check finds condensation forming at the back of the outer render from December, peaking at about 100 g/m² in February and drying out fully in summer, and it stays acceptable across the range of vapour values it tests for the straw. A 25mm cement render outside, which resists vapour about twice as much as lime (μ 20 against 10 in U-Monkey’s defaults), raises the peak to about 590 g/m² in March, and straw that stays damp decays, so keep both coats vapour-open and the walls protected from driving rain with a good overhang and a raised plinth.
Is this calculator free?
Yes — building the element, reading the U-value, the compliance targets (including the Future Homes Standard), the condensation-risk screening check and the thermal-mass figures (decrement factor, time lag, κ) are all free in your browser, and the Building Control-ready PDF report is free too. No sign-up.
Does it follow the official calculation method?
Yes — the combined method of BS EN ISO 6946:2017 with BR 443 conventions, including timber bridging, mortar joints in blockwork (and in solid brickwork where BR 443 §4.2 requires them) and air-gap corrections, BS EN ISO 13370 for ground floors, suspended floors and basements, and ISO 13788 for the condensation screening check.
Other common build-ups
Walls
- U-value of a cavity wall with full-fill insulation
- U-value of a cavity wall with PIR partial-fill insulation
- U-value of a timber frame wall
- U-value of a solid brick wall with internal insulation
- U-value of a one-and-a-half-brick (327.5mm) solid wall
- U-value of a solid wall with external insulation
- What is the U-value of an uninsulated cavity wall?
- U-value of a timber frame wall with PIR insulation outside the studs
- U-value of a solid stone wall with internal insulation
- U-value of a cavity wall with external wall insulation
- U-value of a cavity wall with a dense concrete block inner leaf
- U-value of a solid brick wall (9-inch, uninsulated)
- U-value of a solid stone wall (uninsulated)
- U-value of a cavity wall after cavity wall insulation (blown wool or bead)
- Insulated plasterboard on a solid wall: what thickness reaches a U-value of 0.30?
- U-value of a solid wall battened out with insulation
- U-value of a dormer cheek wall (loft conversion)
- U-value of a garage conversion wall (insulating single-skin brick)
- U-value of a SIP wall (structural insulated panels)
- U-value of an ICF wall (insulating concrete formwork)
- U-value of a light steel frame wall (SFS)
- U-value of a timber frame wall with wood-fibre insulation
- U-value of an I-joist timber frame wall (Passivhaus-level)
- U-value of an extension cavity wall (what reaches 0.18)
- U-value of a wide cavity wall (200mm, 250mm, 300mm)
- U-value of wood-fibre internal wall insulation on a solid brick wall
- U-value of external wall insulation with mineral wool
- U-value of a knee wall in a loft conversion
- U-value of a party wall (0.0, 0.2 or 0.5)
- U-value of a basement wall (heated basement)
- U-value of a cellar wall when converting a cellar (basement conversion)
- U-value of a hempcrete wall (hemp-lime)
- U-value of a wall between a house and an integral garage
- U-value of a wall to an unheated corridor or stairwell in flats
- U-value of a CLT (cross-laminated timber) wall
- U-value of a cob wall
- U-value of aerogel internal wall insulation
- U-value of wood-fibre external wall insulation (EWI) on a solid wall
- U-value of a log cabin wall
- U-value of a garden room (garden office) wall
- U-value of an SFS infill wall with rainscreen cladding
- U-value of a solid aircrete wall (thin-joint blockwork)
- U-value of a shipping container wall
- U-value of a park home wall with external insulation
- U-value of the wall between a house and a conservatory
- U-value of calcium silicate internal wall insulation
- U-value of cork insulation on a solid wall
- U-value of insulating (thermal) plaster on a solid wall
- U-value of brick-slip external wall insulation
- U-value of a tile-hung wall
- U-value of built-up (twin-skin) metal wall cladding
- U-value of an insulated composite panel wall
- U-value of rainscreen cladding on a concrete or blockwork wall
- U-value of a precast concrete sandwich panel
Roofs
- U-value of 270mm loft insulation
- U-value of an uninsulated loft (a ceiling with no insulation)
- U-value of 100mm loft insulation (and what a top-up achieves)
- U-value of 400mm loft insulation
- U-value of insulation between rafters (loft conversion)
- U-value of insulation over the rafters (warm pitched roof)
- U-value of a room-in-roof sloping ceiling
- U-value of a warm flat roof
- Flat roof insulation thickness — about 150mm PIR for 0.15, 140mm for 0.16
- U-value of a cold flat roof (cold deck)
- U-value of an inverted flat roof
- U-value of an uninsulated flat roof (and a warm-deck upgrade)
- U-value of a room-in-roof flat ceiling (collar ceiling)
- U-value of a wood-fibre sarking roof (a vapour-open warm pitched roof)
- U-value of a solid (tiled) conservatory roof
- U-value of a boarded loft (loft boarding over insulation)
- U-value of a green roof (sedum or extensive green roof)
- U-value of a thatched roof
- U-value of spray foam insulation in a pitched roof
- U-value of a cold flat roof converted to a warm roof
- U-value of a garden room (garden office) roof
- U-value of a warm flat roof on a profiled metal deck
- U-value of a roof terrace with paving on pedestals
- U-value of a SIP roof (structural insulated panels)
- U-value of a ceiling insulated from below with insulated plasterboard
- U-value of a garage conversion roof (flat roof insulated from below)
- U-value of a warm flat roof on a concrete deck
- U-value of tapered roof insulation
- U-value of a mansard roof
- U-value of a built-up (twin-skin) metal roof
- U-value of an insulated composite roof panel
Floors
- U-value of an insulated concrete ground floor
- U-value of an insulated suspended timber floor
- U-value of a beam and block floor with PIR
- U-value of a ground floor with insulation below the slab
- U-value of a floor over a garage
- U-value of an uninsulated concrete ground floor
- U-value of an uninsulated suspended timber floor
- Underfloor heating on a ground floor: insulation and U-value
- U-value of insulation laid over an existing concrete floor
- U-value of a garage conversion floor
- U-value of a basement floor (heated basement)
- U-value of an extension floor (and the whole-house perimeter rule)
- U-value of an insulated raft foundation (EPS raft)
- U-value of a limecrete floor (insulated with foamed glass)
- U-value of a garden room (garden office) floor
- U-value of a solid floor with edge insulation
- U-value of a floor over an unheated cellar
- U-value of an exposed floor over a passage, undercroft or overhang
- U-value of a battened timber floor over a concrete slab
- U-value of a suspended timber floor insulated with wood fibre or sheep’s wool
- U-value of a concrete floor over a car park
- U-value of a warehouse floor slab
Different build-up? See the full wall U-value calculator, or start from scratch in the main U-value calculator.
Need the wider compliance picture? U-values feed straight into SAP calculations — or let our New Build Compliance Pack handle the lot. Background reading: what U-values actually are, and why two calculators can give different answers for the same wall.