Water efficiency calculator spreadsheet (Part G)

Most people looking for a Part G spreadsheet want one thing: the arithmetic, done right. Here is the whole methodology — every use factor, the averaging rule, the two adjustments at the end — with a worked example. Then decide whether you still want the spreadsheet.

Free to use, nothing to download. Building Control-ready PDF £25 +VAT (£30 inc VAT).

Launch WaterMonkey — free, no sign-up

Runs in your browser and autosaves. Installs as an app if you want it offline.

See a sample certificate (PDF) →

Is there a Part G water efficiency calculator spreadsheet?

Yes — spreadsheet versions of the water efficiency calculation have been passed around since the methodology was published in 2009, and plenty of practices keep one in a shared drive. There is nothing proprietary inside them. They hold the Table 1 use factors, one averaging rule and two adjustments at the end, and that is the entire calculation. All of it is set out below, so you can work it by hand, rebuild it in a sheet of your own, or let the browser do it.

So the useful question isn't where to find a spreadsheet — it's whether you want to own one. A sheet has to be version-controlled, protected from a stray row insert, and re-checked every time somebody copies it for the next job. The arithmetic is fixed and public either way, which is why we put it in a browser instead: same factors, same rules, live PASS/FAIL, nothing to maintain.

What a Part G spreadsheet actually contains

Less than people expect. Each fitting is scored as capacity × use factor + fixed use, the lines are added up, the total is multiplied by 0.91, and 5 litres per person per day of external use is added. The result has to come in at or below your target — normally 125 l/p/d, or 110 l/p/d where planning imposes the tighter optional standard.

The use factors are published in Table 1 of The Water Efficiency Calculator for New Dwellings, the methodology Approved Document G and Building Regulation 36 require. They never change, which is exactly why this doesn't need to be a document you keep a copy of:

FittingWhat you enterUse factorFixed use
WC, dual flush — fullFull flush volume (l)1.460.00
WC, dual flush — partPart flush volume (l)2.960.00
WC, single flushFlush volume (l)4.420.00
Taps, excl. kitchenFlow rate (l/min)1.581.58
Bath, shower also presentCapacity to overflow (l)0.110.00
Shower, bath also presentFlow rate (l/min)4.370.00
Bath onlyCapacity to overflow (l)0.500.00
Shower onlyFlow rate (l/min)5.600.00
Kitchen / utility tapsFlow rate (l/min)0.4410.36
Washing machineLitres per kg dry load2.10.00
DishwasherLitres per place setting3.60.00
Waste disposal unitFitted or not13.08

Where a machine isn't specified, defaults of 8.17 litres/kg and 1.25 litres per place setting apply. Want these constants machine-readable? They're published as open CSV/JSON. Want to see what each line is worth? Start with shower flow rate — it is usually the biggest number on the page.

A worked example, start to finish

An ordinary specification: a 6/4 dual-flush WC, 6 l/min basin taps, a 180 litre bath with a 10 l/min shower over it, an 8 l/min kitchen tap, and unspecified white goods.

LineArithmeticl/p/d
WC full flush6 × 1.468.76
WC part flush4 × 2.9611.84
Basin taps(6 × 1.58) + 1.5811.06
Bath180 × 0.1119.80
Shower10 × 4.3743.70
Kitchen taps(8 × 0.44) + 10.3613.88
Washing machine8.17 × 2.117.16
Dishwasher1.25 × 3.64.50
Totalsum of the lines130.70
Normalised130.70 × 0.91118.9
Plus external use118.9 + 5.0123.9

123.9 against a 125 target — a pass, with 1.1 litres to spare. That is how tight an ordinary specification is, and it is why the number is worth checking before the sanitaryware is ordered rather than after. It also explains why a late change — a bigger bath, a pumped shower, a waste disposal unit — so often turns a pass into a fail.

Where spreadsheet calculations go wrong

None of these are hard. They are just easy to get wrong once, quietly, in a file nobody re-checks — and that file is the evidence Building Control keeps on record. A spreadsheet will happily carry the mistake forward into every job it is copied into.

What you get instead

Fitting by fitting

If you want to understand a particular line before you change it:

Frequently asked questions

Is there an Excel spreadsheet for the Part G water calculation?

Spreadsheet versions of the water efficiency calculation have circulated since the methodology was published in 2009, and plenty of practices keep one. There is nothing proprietary in them: the Table 1 use factors, the multiple-fittings averaging rule, the 0.91 normalisation and the 5 l/p/d external allowance. All of it is set out in full on this page, so you can build your own sheet from it — or use the free browser calculator and skip the maintenance.

Where can I download a water efficiency calculator spreadsheet?

We do not publish one, deliberately. A downloaded sheet is a copy that ages: a stray row insert or a formula range left behind is the classic way a scheme that looked compliant turns out not to be. If you want the numbers machine-readable, the Table 1 factors and constants are published as open CSV and JSON at energycount.co.uk/data/, free to reuse with attribution. If you want the calculation done, WaterMonkey is free in the browser with live PASS/FAIL.

Do I need a spreadsheet to do a Part G water calculation?

No. The calculation is a fixed set of arithmetic defined by the official methodology, and it runs perfectly well in a browser. WaterMonkey applies the same Table 1 use factors, the same multiple-fittings rule, the same 0.91 normalisation and the same 5 l/p/d external allowance — with a live PASS/FAIL as you type instead of a formula you have to trust.

Is WaterMonkey free?

Yes. Building the fittings schedule, changing specifications and checking PASS/FAIL against 125, 110 or a custom target is free in your browser, with no sign-up. You only pay £25 +VAT (£30 inc VAT) when you export the Building Control-ready PDF, and that one fee covers every identical plot on the site.

Will Building Control accept it?

The export is a dated, branded PDF showing the fittings schedule, the calculated litres-per-person-per-day figure, the target and the PASS result — the same information a spreadsheet-based calculation presents, laid out for a compliance file. The methodology is The Water Efficiency Calculator for New Dwellings, as required by Approved Document G and Building Regulation 36.

Does it handle rainwater and greywater?

Yes — both, using the BS 8515 intermediate calculations or a direct daily figure, with savings capped against the demand they can actually displace and protection against counting the same WC demand twice across two systems. That double-count guard is one of the easiest things to get wrong by hand.

Can I work on it offline?

Yes. WaterMonkey installs like an app from your browser and then works fully offline, autosaving as you go. You only need a connection to export the paid PDF.

What about a site with several house types?

One dwelling type covers every identical plot at no extra cost, and each additional type with a different fittings spec is £15 +VAT. A 40-plot site built to one specification is still £25 +VAT.

Background reading: what Building Control is asking for, the 125 l/p/d standard, and the 110 l/p/d planning condition. Rather hand it over entirely? See our Part G service.

Rather just get the number?

Put your fittings in and WaterMonkey does the whole methodology live — use factors, averaging, normalisation, external allowance — with PASS/FAIL as you type. Free on screen; the certificate is the only paid part.