–Hz
Reading the frequency from Elexon…
The last hour
NESO's normal range, 49.8 to 50.2 Hz 50 Hz
Today so far
What the frequency shows
Britain's grid runs on alternating current at 50 cycles a second, and the big spinning generators in its gas, nuclear, biomass and hydro power stations turn in step with it. While more power is being drawn from the grid than is being generated, the difference comes from the energy stored in all that spinning mass, and the machines slow a little: the frequency falls. While more is generated than drawn, they speed up and it rises; while the two match, it holds steady. So the frequency is a live measure of the balance between supply and demand across the whole of Great Britain, practically the same everywhere on the grid at any moment. A frequency below 50 Hz that is rising means the balance has already tipped back the other way.
How NESO keeps it near 50 Hz
NESO balances supply and demand ahead of time and minute by minute, and holds "frequency response" in reserve for the seconds in between: batteries and other providers that sense the frequency themselves and push power in or take it out, the fastest within about a second. Dynamic Regulation nudges it back all the time, Dynamic Moderation acts fast as it nears the edge of the normal range, and Dynamic Containment catches a sudden big loss. The spinning mass of the big generators, the grid's inertia, slows how fast the frequency can change, which gives them time to act.
The limits
- 49.8 to 50.2 Hz: NESO's normal operating range, its own guideline for everyday running.
- 49.5 to 50.5 Hz: the legal limits, 50 Hz plus or minus 1% (the Electricity Safety, Quality and Continuity Regulations 2002).
- 49.2 Hz: after the sudden loss of a big power station or cable, NESO plans for the frequency to stay above this.
- 48.8 Hz: automatic protection starts disconnecting customers (low frequency demand disconnection), to stop a total blackout.
When it went wrong: 9 August 2019
At 16:52 on Friday 9 August 2019, lightning struck a 400 kV line north of London. Within about a second Hornsea One offshore wind farm cut its output by 737 MW and a steam turbine at Little Barford power station (244 MW) tripped, along with about 500 MW of smaller generators; a gas turbine at Little Barford followed a minute later. The frequency fell to 48.8 Hz and automatic protection disconnected 931 MW of demand: about 1.1 million customers lost power and trains stopped. The frequency was back at 50 Hz within five minutes, and every customer was reconnected within 45 minutes.
Where the readings come from
The readings are NESO's, one every 15 seconds, which Elexon publishes in batches every couple of minutes, so the latest here is usually a minute or two old. This page reads them in your browser every 30 seconds while it's open. The same dial is in GridMonkey, beside the live generation mix.
GridMonkey → Every power station, live → Wind farms turned down now → Outages now →
Contains BMRS data © Elexon Limited copyright and database right 2026 (licence).