Appendix D: all 495 printed values
The opening area of a window comes from Appendix D. Its Tables D1 to D9 print 495 equivalent areas: nine opening angles, eleven heights and five widths. Where a window’s size and angle are on that grid, O-Monkey uses the printed value. For every other size it uses the discharge-coefficient calculation the tables come from — the ESFA ClassVent method Appendix D refers to — which on its own reproduces all 495 printed values to two decimal places, and gives ClassVent’s own worked figure: a 1 m × 1 m opening at 10° has a discharge coefficient of 0.18719 and an equivalent area of 0.3019 m². The site is rebuilt from the same code, and the build stops if either figure changes. Every window in a report names which of the two it used. Try it on any window.
Written twice
The checks have been written twice: once in O-Monkey, and once as a separate program, in a different programming language, written from Approved Document O, the MHCLG FAQ and the Future Homes Hub guidance rather than from O-Monkey’s code. Before a release, every worked example goes through both, and they must agree check by check: the glazing, the most glazed room, every window’s opening area, the total and every bedroom, in every direction the home could face.
A test for every rule
Each rule has its own automated tests, with the paragraph it comes from in the test’s name:
- The risk band: all 207 districts of Appendix C, Table C1, the districts it lists only by sub-district, the central Manchester note, and postcodes outside England.
- Orientation: the nearest of 16 compass points, the stricter row exactly between two (MHCLG FAQ 4 and 5), and left and right as seen from the front.
- Cross-ventilation: openings on opposite façades only; a corner does not count (para 1.4).
- The glazing limits: Tables 1.1 and 1.2, judged on the unrounded figure, with the high-risk limits and shading for a west-facing home (MHCLG FAQ 2).
- The most glazed room: the room with the most glass, in m² (Future Homes Hub guidance), and only that room against the cap.
- Shading: glass facing north-east round to north-west via south, in the high-risk location (para 1.9).
- The opening area: the greater of the floor and glazing percentages (Tables 1.3 and 1.4), and every bedroom’s own minimum.
- Each window: top-hung windows with height and width swapped, centre-pivots as two halves, sashes and sliders on their clear opening at 90°, restrictors in the restricted position (MHCLG FAQ 8).
- The 650 mm handle rule: reveal plus the leaf’s swing no more than 650 mm (para 3.9a, MHCLG FAQ 15), on every floor.
- Falling and security: upper-floor openings without guarding counted as 100 mm (paras 3.8–3.9), ground-floor and easily accessible bedrooms counting only secure openings at night (paras 3.6–3.7).
- When the method can’t be used: night-time noise (para 3.1) and communal heating pipework in flats (para 1.13).
- House types: the same answers for a plot as for the design turned to face that way, and handed plots mirrored, not just turned.
Around them sit the tests of the app itself — the start screen, the house picture, the window editor, the table, the schedule import from spreadsheets and PDFs, the report, saving and sharing — on a computer screen and a phone. Close to 500 automated checks run before each release.
The worked example, checked on every build
The example on the O-Monkey page — 88 m², 9 windows and doors, in BH16 — is worked out by the same engine when the site is built: 12.60 m² of glass against a 18% limit, 7.98 m² of opening area against 7.92 m² needed. If a change to the code moved any of it, the page would not build.
Where the document is silent
Approved Document O leaves some questions open. Where it does, O-Monkey follows the published guidance below, and every report says so:
- The most glazed room
- Approved Document O does not define it. O-Monkey follows the Future Homes Hub Part O guidance: the room with the most glass in m²; where two tie, the one with more glass for its floor area.
- Sliding and bifold doors
- Not mentioned in the document. Assessed like a sliding sash on their clear opening at 90° (Appendix D), one pane of a slider counting (Future Homes Hub guidance).
- The front door
- Its glass counts towards the limits; its opening does not, because it cannot be left open securely (Future Homes Hub guidance).
- The 650 mm rule on the ground floor
- Paragraph 3.9a sits under protection from falling, but gives no exemption for ground-floor windows, so O-Monkey applies it on every floor.
- Top-hung roof windows
- Counted in their centre-pivot position, fully open at 90°, as two halves: most top-hung roof windows also pivot, and that is the position used for ventilation.
- Rooflight glass
- Counted in the glazing totals and the room it lights, but not in deciding which side of the home is the most glazed.
What is not tested
O-Monkey checks what you enter. It cannot check that the sizes match the drawings, or that the windows fitted match the schedule. It flags entries that look like slips — a size typed in metres, glass bigger than its frame, rooms that add up to more than the whole home — but it never changes a figure for you. Compliance is decided by the building control body, and Part 2a of the Appendix B checklist is signed by the person competent to design the home. The common mistakes are the ones worth checking twice.
Reports you can verify
Every paid report carries a Report ID and a QR code. Entering the ID at energycount.co.uk/verify confirms the report was produced by O-Monkey and when; adding the PDF there confirms it has not been altered since.
Frequently asked questions
How do I know O-Monkey gets Appendix D right?
Approved Document O’s Tables D1 to D9 print 495 equivalent areas: nine opening angles, eleven heights and five widths. O-Monkey uses the printed value wherever a window’s size and angle fall on that grid, and the discharge-coefficient calculation the tables come from for every other size. That calculation alone reproduces all 495 printed values to two decimal places, and the site will not build if it stops doing so.
Has anyone checked the calculation independently?
The checks have been written twice: once in O-Monkey, and once as a separate program in a different language, written from the Approved Document rather than from O-Monkey’s code. Every worked example must give the same answer, check by check, in both before a release.
Does a passing result mean Building Control will accept it?
No. O-Monkey checks what you enter, exactly as the document says, and shows its working; it cannot check that the sizes match the drawings, or that the windows fitted match the design. The building control body decides compliance, and Part 2a of the checklist is signed by the person competent to design the home.
What if I find a mistake?
Tell us: info@energycount.co.uk or 01202 623236. A report that misapplies the stated method is repaired, replaced or refunded, and the fix goes into the tests so it cannot come back.
Related: how to use O-Monkey · the 650 mm handle rule · common mistakes.
Sources: Approved Document O (2021 edition) · Approved Document O frequently asked questions (MHCLG) · the Future Homes Hub Part O technical guidance (2022) · the ESFA ClassVent discharge coefficient calculator.